17.) Is the IRIG signal modulated or demodulated?

The IRIG signal is demodulated (dc level-shifted digital signal). See Section 1, General

Information; Section 6, Reporting and Alarms; and Section 12, Installation, for additional

information.


18.) Can the IRIG signal be daisy-chained to multiple BE1-CDS240 units?

Yes, multiple BE1-CDS240 units can use the same IRIG input signal by daisy-chaining the

BE1-CDS240 inputs. The burden data is non-linear, approximately 4 kilo-ohms at 3.5 Vdc and 3

kilo-ohms at 20 Vdc. See Section 1, General Information; Section 6, Reporting and Alarms; and

Section 12, Installation, for additional information.


19.) How can I find out the version number of my BE1-CDS240?

The application version can be found in three different ways.

1) Use the HMI, Screen 4.6.
2) Use the ASCII command interface with the RG-VER command.
3) Use BE1-CDS240 BESTCOMS (the version is provided on the General Operation

Screen, Identification Tab).

20.) How are reports and other information obtained from the relay saved in files for future

use?

Through BESTCOMS, select print from the dropdown menu and then select RTF export, which

allows the user to save the file to any location. In addition, text transferred from the relay to your

terminal emulation software can be selected and copied to the clipboard. The clipboard

contents are pasted into any word processor such as Microsoft® Notepad and saved with an

appropriate file name.