17.) Is the IRIG signal modulated or demodulated?
The IRIG signal is demodulated (dc level-shifted digital signal). See Section 1, General
Information; Section 6, Reporting and Alarms; and Section 12, Installation, for additional
information.
18.) Can the IRIG signal be daisy-chained to multiple BE1-CDS240 units?
Yes, multiple BE1-CDS240 units can use the same IRIG input signal by daisy-chaining the
BE1-CDS240 inputs. The burden data is non-linear, approximately 4 kilo-ohms at 3.5 Vdc and 3
kilo-ohms at 20 Vdc. See Section 1, General Information; Section 6, Reporting and Alarms; and
Section 12, Installation, for additional information.
19.) How can I find out the version number of my BE1-CDS240?
The application version can be found in three different ways.
1) Use the HMI, Screen 4.6.
2) Use the ASCII command interface with the RG-VER command.
3) Use BE1-CDS240 BESTCOMS (the version is provided on the General Operation
Screen, Identification Tab).
20.) How are reports and other information obtained from the relay saved in files for future
use?
Through BESTCOMS, select print from the dropdown menu and then select RTF export, which
allows the user to save the file to any location. In addition, text transferred from the relay to your
terminal emulation software can be selected and copied to the clipboard. The clipboard
contents are pasted into any word processor such as Microsoft® Notepad and saved with an
appropriate file name.