Basler Electric BE1-59N User Manual
Page 18
![background image](https://www.manualsdir.com/files/773835/content/doc018.png)
Locator
Description
D
Undervoltage Time Dial. Pushbutton switch that selects the desired overvoltage output
delay, either definite time (from 00.1 to 99.9 seconds) or, inverse time (characteristic
curves 01 through 99). A setting of 00 is instantaneous in either case.
E
Power Indicator. This red LED lights when operating power is applied to the relay.
F
Target Reset Switch. This switch is operated to reset the target indicators.
G
Target Indicators. The electronically latched red target indicators illuminate when the
corresponding output relay energizes. To ensure proper operation of current-operated
targets, the current flowing through the trip circuit must be 200 mA or higher. Target
indicators are reset by operating the target reset switch (locator F).
H
Output Test Pushbuttons. These pushbuttons allow manual actuation of the output relays.
Output relay actuation is achieved by inserting a nonconductive rod through the front
panel access holes.
I
Undervoltage Pickup LED. A red LED that illuminates when undervoltage exceeds the
pickup setting.
J
Undervoltage Pickup Adjustment. A multiturn potentiometer that sets the undervoltage
comparator threshold voltage. Continuously adjustable over the range indicated by the
style chart.
K
Inhibit LED. A red LED that illuminates when the monitored generator voltage is under the
inhibit set point.
L
Inhibit Pickup Adjustment. Multiturn potentiometer that sets the inhibit comparator
threshold so that whenever generator voltage falls below the set point, the (optional)
undervoltage measuring circuitry is inhibited from operation.
2-2
BE1-59N Controls and Indicators
9171400990 Rev K