Maintenance, Storage, Maintenance -4 – Basler Electric BE1-50/51B-237 User Manual
Page 36: Storage -4, Figure 4-3. coordination timing diagram

4-4
BE1-50/51B-237/-238 Installation
9252000899 Rev B
From the reset characteristic curve equation:
1
2
−
=
M
RD
T
R
M equals 0 if current goes to zero. A negative result indicates reset time.
seconds
15.5
1
0
2
7.75
2
−
=
−
×
=
Result: Full trip = 0.209 seconds and full reset = 15.5 seconds if current goes to zero.
In Figure 4-3:
T
A
= 0.209 seconds (relay was at reset)
T
B
= value A because rewind has not gone to zero T C = value A because rewind has not gone to zero Figure 4-3. Coordination Timing Diagram Maintenance BE1-50/51B-237 and BE1-50/51B-238 relays require no preventative maintenance other than periodic checking of relay connections to make sure that they are clean and tight. If the relay fails to function properly, contact the Technical Sales Support department of Basler Electric. Storage This device contains long-life aluminum electrolytic capacitors. For devices that are not in service (spares in storage), the life of these capacitors can be maximized by energizing the device for 30 minutes once per year.