Radio frequency interference (rfi), Vibration, Shock – Basler Electric BE1-50/51B-218 User Manual
Page 19: Environment, Agency recognition, Gost-r certification, Physical, Environment -9, Agency recognition -9, Physical -9

9252000995 Rev H
BE1-50/51B-218/-228 General Information
1-9
Radio Frequency Interference (RFI)
Field-tested using a 5-watt, hand-held transceiver operating at random frequencies centered around 144
MHz and 440 MHz, with the antenna located 6 inches from the relay in both horizontal and vertical
planes.
Vibration
Withstands 2 G in each of three mutually perpendicular planes swept over the range of 10 to 500 Hz for a
total of 6 sweeps, 15 minutes each sweep.
Shock
Withstands 15 G in each of three mutually perpendicular planes.
Environment
Operating Temperature:
–40
C to 70C (–40F to158F)
Storage Temperature:
–50
C to 70C (–58F to 158F).
Agency Recognition
GOST-R Certification
GOST-R certified per the relevant standards of Gosstandart of Russia.
Physical
Case Size:
S1 (Refer to Section 4, Installation for case dimensions.)
Weight:
6.4
lb
(2.77
kg)