Frequency response, Transient response, Harmonic response – Basler Electric BE1-50/51B-218 User Manual
Page 17: Frequency response -7, Transient response -7, Harmonic response -7, Figure 1-3. burden characteristics -7

Figure 1-3. Burden Characteristics
Frequency Response
A change of ±5 Hz from the nominal 50/60 Hz current causes <0.5% change in the current required for
pickup.
Transient Response
<10% overreach with system time constants up to 40 ms.
Harmonic Response
Figure 1-4 shows that a relay set for 1 ampere pickup would pick up at 0.96 amperes with a current
containing 40% seventh harmonic. This corresponds to a 10:1 rejection ratio. Other conditions may be
evaluated in the same manner.
9252000995 Rev H
BE1-50/51B-218/-228 General Information
1-7
This manual is related to the following products: