BE1-50/51B-231 Controls and Indicators

2-3

Table 2-1. BE1-50/51B-231 Controls and Indicators (Refer to Figures 2-1 and 2-2)

Locator Control or Indicator

Function

A

INST MANUAL TRIP

Test Points

When shorted, the test points (jacks) provide a secure means to

manually trip the controlled breaker. Jacks accept a standard 0.08

inch diameter phone tip plug.

B

INST PICKUP

Selectors

Two switches (TENS and UNITS) to select pickup current in

amperes. Changing switch selectors while the relay is in service

may cause tripping.

C

Targets

Red target indicators latch when the trip circuit current is greater

than 0.2 amperes. One target each for TIME and INST.

D

TIME PICKUP

Selectors

Two switches (UNITS and TENTHS) to select pickup current in

amperes. Changing switch selectors while the relay is in service

may cause tripping.

E

CURVE Selector

Ten position selector switch to select one of nine inverse functions

or one fixed time function.

F

TIME DIAL Selectors

Two selector switches (UNITS and TENTHS) to select the desired

characteristic curve. A setting of 0.0 results in instantaneous

operation without any intentional delay. A setting of 9.9

corresponds to the typical time provided by an electromechanical

relay at its maximum dial setting.

G

TIME MANUAL TRIP

Test Points

When shorted, the test points provide a secure means to manually

trip the controlled breaker. Jacks accept a standard 0.08 inch

diameter phone tip plug.

H

ACTIVE/PICKUP LED This bicolor LED indicates the level of current sensed by the relay.

A green LED indicates that the relay is active but not picked up.

The LED changes to red when the sensed current exceeds the

time overcurrent pickup setting. The LED changes from red to

green when the sensed current decreases below 95% of the time

overcurrent pickup setting.
Note: A minimum of 0.5 A is required to light the LED. The LED

may not turn green (active) before turning red (picked up) at the

0.5 A pickup setting.

I

Target

RESET Button

Linkage extends through back of front cover to reset both gravity

latched target indicators.

SW3

SW3-1

SW3-1 provides an additional instantaneous delay of 0.2 second

when closed (ON). Closing both SW3-1 and SW3-2 provides an

additional instantaneous delay of 0.3 second.

SW3-2

SW3-2 provides an additional instantaneous delay of 0.1 second

when closed (ON). Closing both SW3-2 and SW3-1 provides an

additional instantaneous delay of 0.3 second.

SW3-3

SW3-3 provides selection of GE IAC type curves or ABB type

curves. Closing switch SW3-3 (ON) selects GE IAC type curves

(refer to Table 1-3). Opening switch SW3-3 (OFF) selects ABB

type curves (refer to Table 1-2).

SW3-4

SW3-4 provides selection of either instantaneous or integrating

reset characteristics. Closing SW3-4 (ON) selects integrating reset

characteristics. Opening SW3-4 (OFF) selects instantaneous reset

characteristics.