Integrating reset, Instantaneous overcurrent (50) element, Pickup – Basler Electric BE1-50/51B-231 User Manual

Page 14: Dropout, Instantaneous overcurrent (50) element -4, Figure 1-1. integrating reset characteristic curve

background image

1-4

BE1-50/51B-231 General Information

9252000895 Rev C

† Figure numbers refer to the characteristic curves located in Appendix A, Time Characteristic Curves.
‡ Curves B and C are defined in British Standard BS142 and IEC Standard IEC 255-4.
§ Fixed time delay, adjustable from 0.1 to 9.9 seconds.

Reset begins when the current drops below 95% of pickup. Integrating reset simulates the disk reset of

electromechanical relays. BE1-50/51B-231 relays provide the integrating reset function even when input

current falls to zero.

Integrating Reset

Integrating reset characteristics are defined by the following equation and shown in Figure 1-1. Equation

constants are provided in Tables 1-2 or 1-3.

Integrating Reset Equation:

1

M

RD

T

2

R

=

Where:

T

R

= Time to reset in seconds

R = Constant for the particular curve

D = TIME DIAL setting

M = Current in multiples of PICKUP setting during reset

Figure 1-1. Integrating Reset Characteristic Curve

Instantaneous Overcurrent (50) Element

Setting the INST PICKUP control at the minimum pickup setting places the relay in the most sensitive

state and may be used as a safety setting.

Setting Range ............................ 1 to 99 Aac

Pickup

Setting Increment ....................... 1 Aac

Accuracy .................................... ±2%, ±25 milliamperes at or above 1.0 ampere setting

Dropout occurs at 95% of pickup value.

Dropout

1.0

10.0

100.0

0.000

0.200

0.400

0.600

0.800

1.000

1.200

Multiple of Pickup

xR

D

(S

ec

on

ds

)

P0

04

6-

11

Vertical axis xRD (Seconds) is applicable for all curves and is derived from

multiplying the constant R for the curve selected times D (the Time Dial setting).