Basler Electric BE1-50/51B User Manual
Page 15

9252000991 Rev R
BE1-50/51B General Information
1-3
Table 1-1. BE1-50/51B Overcurrent Relays, One Ampere CT Secondary, 50/60 Hz
Model Number
Case Style
SW3-3 Selects
Sensing Input Range (Amps)
TIME
INST
BE1-50/51B-101
A1
0.2 Second Delay
0.1 - 3.18
0.2 - 19.8
BE1-50/51B-201
A1
Curve Set
0.1 - 3.18
0.2 - 19.8
BE1-50/51B-102
S1 (Projection Mount)
0.2 Second Delay
0.1 - 3.18
0.2 - 19.8
BE1-50/51B-202
S1 (Projection Mount)
Curve Set
0.1 - 3.18
0.2 - 19.8
BE1-50/51B-103
S1 (Semi-Flush Mount)
0.2 Second Delay
0.1 - 3.18
0.2 - 19.8
BE1-50/51B-203
S1 (Semi-Flush Mount)
Curve Set
0.1 - 3.18
0.2 - 19.8
Table 1-2. BE1-50/51B Overcurrent Relays, Five Ampere CT Secondary, 50/60 Hz
Model Number
Case Style
SW3-3 Selects
Sensing Input Range (Amps)
TIME
INST
BE1-50/51B-105
A1
0.2 Second Delay
0.5 - 15.9
1.0 - 99.0
BE1-50/51B-205
A1
Curve Set
0.5 - 15.9
1.0 - 99.0
BE1-50/51B-106
S1 (Projection Mount)
0.2 Second Delay
0.5 - 15.9
1.0 - 99.0
BE1-50/51B-206
S1 (Projection Mount)
Curve Set
0.5 - 15.9
1.0 - 99.0
BE1-50/51B-107
S1 (Semi-Flush Mount)
0.2 Second Delay
0.5 - 15.9
1.0 - 99.0
BE1-50/51B-207
S1 (Semi-Flush Mount)
Curve Set
0.5 - 15.9
1.0 - 99.0
NOTE: 100 series relays (e.g. - BE1-50/51B-105) have the integrating reset function when there is
adequate input current to power the relay. 200 series relays (e.g. - BE1-50/51B-205) have the integrating
reset function even when the input current falls to zero.