beautypg.com

Venting installation instructions – Desa (V)VC42NE User Manual

Page 7

background image

7

7

www.desatech.com

116237-01A

VENTING INSTALLATION

INSTRUCTIONS

NOTICE: Read these instructions completely before

attempting installation.

These models are tested and approved for use with DESA (direct-

vent) pipe components and terminations.
The venting system must terminate on the outside of the structure and

can not be attached to a chimney or flue system serving a separate

solid fuel or gas burning appliance. A direct-vent appliance must have

its own venting system. DO NOT common vent this appliance.
These models are approved to be vented either horizontally through

an outside wall or vertically through a roof or chase enclosure using

the following guidelines:
• When venting system terminates horizontally on an outside

wall, you may install a standoff if the termination cap is to be

installed directly on a combustible finish such as vinyl, wood,

stucco, etc.

• Never run the vent downward as this may cause excessive tem-

peratures which could cause a fire.

• Vent pipe air space clearances to combustibles are 1" on all sides

except on the horizontal sections, which requires 2" clearance

from the top of the pipe. Where the termination cap penetrates

a combustible wall, 1" air space clearance is required.

• Snorkel terminations are required when minimum clearance to grade

cannot be met (see Figure 16 on page 11).

• Have fireplace and selected vent components on hand to help

determine the exact measurements when elbowing or offsetting.

Always use wall firestops when penetrating walls and firestops

when penetrating ceilings or attic spaces.

• Install horizontal venting with a 1/4" rise for every 12" of run

toward the termination.

WARNING: Read all instructions completely and

thoroughly before attempting installation. Failure to

do so could result in serious injury, property damage

or loss of life.

IMPORTANT:

Do not seal vent cap to pipe. Cap must be remov-

able for service.

NOTICE: Failure to follow these instructions will void

the warranty.

INSTALLATION PRECAUTIONS

• Wear gloves and safety glasses for protection
• Use extreme caution when using ladders or when on roof tops
• Be aware of electrical wiring locations in walls and ceilings
The following actions will void the warranty on your venting

system:
• Installation of any damaged venting component
• Unauthorized modification of the venting system (Do not cut

or alter vent components)

• Installation of any component part not manufactured or

approved by DESA

• Installation other than as instructed by these instructions

WARNING: This gas fireplace and vent assembly

must be vented directly to the outside. The venting

system must NEVER be attached to a chimney serv-

ing a separate solid fuel burning appliance. Each

direct-vent gas appliance must use a separate vent

system. Do not use common vent systems.

WARNING: Vent pipe air space clearances to com-

bustibles are 1" on all sides except on the horizontal

sections, which require 2" clearances from the top of

the pipe. Where the termination cap penetrates a com-

bustible wall, 1" air space clearance is required.

VENTING INSTALLATION INSTRUCTIONS

Installation Precautions