Facing Requirements

NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it

does, it is considered a mantel and must meet the mantel requirements listed in this manual.

Adhesive

WARNING

: Do not use adhesive to secure the cement board or facing. The high

temperatures of the fireplace may cause adhesives to emit odors. Use mastic or thin set (or
other non-combustible, non-odorous adherent) to attach the facing to the cement board.

NOTE: Screws may be used to secure the cement board to the fireplace. Do not penetrate
the fireplace more than 3/4”

6" Min.
(both sides)

Non-combustible Facing

The fireplace requires a concrete board (or other

non-combustible) extending from the header to

the floor and to the framing members on both

sides. Do not use sheetrock, plywood or other

combustible material.

Arch Face

Rectangular Face

12" Min.

Header

Bottom of

Faceplate

NO DRYWALL

1-1/2"

Base of

Fireplace

See “Face Dimensions”

for face sizing.

Facing Over 1" Thick

W A R N I N G

:

Faces that attach with latch-hooks
(Avalon Rosario, Avalon Cambridge,
Avalon Salish Bay, Avalon Rawhide,
Lopi Discovery, Lopi Heritage Bay, FPX
Architectural Faces (all styles),
require a 5/8” gap above the
f a c e

for face installation and removal.

If the facing material is over 1" thick
(e.g. brick, river rock), install the facing
around the perimeter of the face. You
may wish to make a facing support (see
the illustration to the right). If using an
arch face, you may wish to order the
optional set-up face:

Arch Set-Up Face is available from
Travis Industries (Part # 98500697)

Artisan faces vary in size. Use the face
being installed to create a template.

Make a facing support using

2x4’s. It should be 1/8” larger

than the finished face. NOTE:

The bottom of the face is 1-1/2”

above the base of the fireplace.

1-1/2”

Note: if using a brick hearth, the fireplace will need to be raised to accommodate the 1-1/2” gap betwen the

face and the base of the fireplace. For 2-1/2” thick brick this works out to approximately 1-1/8”.

The brick facing must meet the same requirements

listed in “Facing Requirements”.

Center

Line

Rectangular Faces

Use the optional Arch

Set-Up Face available

from Travis

Industries.

Arch Faces

Face Sizing:

See “Face

Dimensions” for

sizing.