- A - 3 -
Optional Features
Model CA Cascading Safety Light Curtain
Figure 1: Standard RSD
Figure 2b: Auto Blank
Figure 2c: 52-260 RSD and corresponding chart
= Terminal #1
J Designators = Connectors
F Designators = Fuses
F1 = 1A slo-blo fuse
J1
ForAB/FBkeyswitch
J2
Leftsetofpins
ActivatesLatchingOutputswhenjumpered
J2
CentersetofPins
FactoryUseonly
J2
Rightsetofpins
ActivatesCincinnatiInterfacewhenjumpered
J3
1
.
+24vdcpowerinput(0.1A)
J3
2
Ground
J3
3
CAN_H(Greenwire)
J3
4
CAN_L(Whitewire)
J4
1
InputfromCincinnatiInterfacePress
J4
2
InputfromLatchingOutputResetbutton
J5
FactoryUseonly
Remote Status Display (RSD)
Description: Allows AutoBlank and/or FloatingBlank optional features to be added to the Model SS.
Includes a four character diagnostics / status display.
Operation:
Allows you to view current feature modes and status as well as fault conditions.
The Yellow status light indicates when you are in any blanking mode.
Manual Latching Reset:
Install jumper on the left 2 vertical pins of J2, to enable Manual latching reset feature.
Install a N.O. push button between J4 (right terminal) and +24vdc.
To reset after blocking the guard, you must clear the guard then push the N.O. button.
Cincinnati Interface (manual output Test):
If you apply +24vdc to Pin 1 of J4 (left terminal), the display will show a “CINN” and force the “RED” shutting down
both outputs 1 & 2.
This allows a remote device to manually check that both outputs can and will shut OFF.