Operation
Emotron AB 01-2550-01r3
7.2
Auto Set
The alarm load level is automatically set by the Auto set function, see Chapter 8
The value for a parameter, e.g. seconds, kW, HP or margin, can only be set as
0, 1, 2, 4, 8, 16, 32 or 64. Select closest value.
The Emotron M10 with article number 01-3160-00 "Fast Response" (M10 FR)
is identical with the standard Emotron M10 except for where the start-up delay
and the response delay are shorter than below:
•
Article number 01-2487-10 standard Emotron M10:
RESPONSE DELAY: 0.05 - 64 s
START-UP DELAY: 1 - 64 s
•
Article number 01-3160-00 "Fast Response" (M10 FR):
RESPONSE DELAY: 0.05 - 6.4 s
START-UP DELAY: 0.1 - 6.4 s
PAR
VAL
RESET 3s.
Rated Power
Relay Inverted
Alarm Current=0
Max Or Min
Response Delay
Start Delay
Margin
Auto Set
64
32
16
8
4
2
1
0
Power /
Alarm
11
L2
13
L3
9
L1
8
NO
7
NC
6
C
2
S2
1
S1
5
RES
M10
PAR
Parameter change
(LED light constant
green) - pressing PAR
key when parameter is
displayed proceeds to
next parameter.
VAL
Value setting - Pressing
VAL key when green LED is
flashing increases value. A
changed value is con-
firmed by pressing PAR.
Reset input
Terminal 5 and 6 are used
for external reset and selec-
tion of latched/unlatched
alarm.
Current input
Terminal 1 and 2. Cur-
rent Transformer; CTM
010, 025 or 050 (Max.
50 A motor).
Relay output
Terminal 6, 7 and 8 output
relay.
Motor terminals
Terminal 9 (L1), 11 (L2)
and 13 (L3) for supply and
motor voltage input.
Power/Alarm
The Power/Alarm LED
turns green at "power
on" and at normal load.
Red at alarm.
Reset
Reset a latched alarm
by pressing both PAR
and VAL at the same
time for 3 seconds.