Hint, Alternative example for single-phase connection, Fig. 2 – Crompton Controls M10 User Manual
Page 11
Emotron AB 01-2550-01r3
Wiring
9
Hint
If the START/STOP is connected as per Fig. 1, it is recommended that termi-
nals 6 and 7 be bypassed during settings. After the settings are completed the
bypass must be taken out.
Please use the enclosed plastic (rubber) insert (if ordered, optional) to cover the
monitor terminals.
Alternative example for single-phase connection
This wiring example shows the alternative connection to be made with regard to
a single-phase connection. Refer to Fig. 1 for the remaining wiring.
Fig. 2
Single-phase wiring example (alternatively see Fig. 10, page 28)
NOTE: The current transformer (CTMxxx) must be placed in the same phase
that is connected to terminal 9, phase L1, see Fig. 1. Make sure that the
Emotron M10 voltage range e.g. 3x100-600 VAC matches the connected
motor/line voltage, e.g. 3x400V.
K1
L
N
M
M10
NC
NO
C
L1
L3
L2
S2
S1
RES
L1
N
CTMxxx
9
11
13
1
2
6
7
8
5