Configuration of sntl150-p via ttl – Computronic Controls Sentinel 150P User Manual
Page 26

SNTL150P-PCSUITE installation & operation
ci0052 p26/28 issue 2 2014-01-09
Configuration of SNTL150-P via TTL
In order for customers to transmit their own remote profiles to the SNTL150P, the following protocol must be
used:
Packet must be sent in the following format
[Byte1] Node Address must be that of the charger (Preset of 100)
[Byte2] Write Multiple Registers (0x10)
[Byte3] Starting Address (High Byte)
[Byte 4] Starting Address (Low Byte)
[Byte 5] Number of Registers {High Byte)
[Byte 6] Number of Registers (Low Byte)
[Bytes 7 – 20] Data as per below
Register start address = 11
Number of points = 7
Register
SNTL150P Function
Scaling
40011
Float voltage
Voltage X 10
40012
Boost voltage
Voltage X 10
40013
Boost initiate voltage
Voltage X 10
40014
Boost period
Minutes
40015
Low alarm voltage
Voltage X 10
40016
High alarm voltage
Voltage X 10
40017
(High Byte) Number of cells
Cells X 1
(Low Byte is reserved, the value stored
must be read and then rewritten to
SNTL150P when updating profile)
The confirmation message back will match Bytes 1
– 6 of transmitted message. Changes are made instantly.