ABUS Technologies Temp DM WM Temperature Transmitter User Manual
Page 9
ABUS TECHNOLOGIES INC.
9
Temp DM-
WM
ATxConfig Main Window
The fields, in the above ATxConfig main window, are described as under:
1. Measuring range: Defines the beginning and the end of the transmitter humidity
and temperature range.
a. Lower Value: sets the value of the input signal associated to the 4 mA output.
b. Upper Value: sets the value of the input signal that will correspond to the 20
mA output.
When the lower limit is defined with a value higher than the higher limit the output
current operates from 20 to 4 mA. The values configured in these fields can not be
beyond the sensor measuring range. The minimum span value has to be observed as
well.
2. Sensor Failure Detection: Establishes the transmitter output behavior (upscale or
down-scale) in the presence of a sensor fail. When Minimum is selected, the output