Dimensions – ABUS Technologies Temp DM WM Temperature Transmitter User Manual
Page 5

ABUS TECHNOLOGIES INC.
5
Temp DM-
WM
IMPORTANT NOTE:
No accuracy improvement results from narrowing the range for the 4-20 mA output. For
example, the specified accuracy will be achieved for a transmitter configured to a -50 to 100 °C or to a
20 to 40 °C range.
Shall any error occur in the measures taken by the sensor, they can be corrected with the
ATxConfig software. The ATxConfig interface can be connected to the transmitter even connected to
the process and under operation. See Figure 03 and Zero Correction field in the main screen of the
ATxConfig software.
3. DIMENSIONS
The Temp-DM (Duct Mount) model transmitter should be installed with a flange.
This flange is first screwed onto the duct wall and the transmitter probe is then inserted
into the flange central hole and locked. Figure Mounting Flange for Temp-DM, below
shows flange dimensions and holes. It is also available in stainless steel or polyamide
6.6.
Mounting flange for Temp-DM.
The probe is made in stainless steel, with standard lengths of 150 mm and 250 mm.
Model Temp-DM dimensions.