Unit display and interface cont, Mui menu navigation – WaterFurnace Envision Hydronic (NDW) User Manual
Page 24
24
NDW INSTALLATION MANUAL
Unit Display and Interface cont.
MUI Menu Navigation
Welcome
Info Temp Stat Outputs Settings Maint Alarm_History
Dual Stage
Info
Outputs
Comp1 Status
ON
Comp2 Status
OFF
Acc1 Status
OFF
Stg1 Status
Normal
Stg2 Status
Normal
BO7 OFF
BO8 OFF
BO9 OFF
EXPB01 OFF
EXPB02 OFF
EXPB07 OFF
EXPB08 OFF
Outputs
Status
Unit Status
Auto
Y1 Status
OFF
Y2 Status
OFF
O Status
OFF
Emerg Shutdown OFF
Current Sens1
OFF
Current Sens2
OFF
Load Flow
OFF
Src Flow
OFF
Low Pres1
ON
Hi Pres1
OFF
Low Pres2
ON
Hi Pres2
ON
Comp1 Low Limit NML
Comp2 Low Limit NML
Stat
Temperatures
Enter Load
77.2°F
Leave Load
51.0°F
Enter Source
70.0°F
Leave Source
66.0°F
Source Frz1
77.8°F
Source Frz2
30.0°F
Load Frz1
30.0°F
Load Frz2
30.0°F
Src Frz Setpt
30.0°F
LD Frz Setpt
30.0°F
Temp
Settings
Unit of Measure F
Settings
Water-to-Water
PRODCWWE-08B
MM/DD/YY
Maintenance
Y1 Input
Auto
Y2 Input
Auto
O Input
Auto
Emerg SD
Auto
Acc1 Sel
ON Comp
Lead/Lag Select OFF
Low Frz Setpt
15°F
Hi Frz Setpt
33°F
Acc1 Dly
9 S
Maint
ALARM SUMMARY
^/High Pressure
Alarm
Alarm lock-outs are reset by cycling power, by pressing the “ESC” and
Return keys simultaneously for a minimum of 15 seconds.
Test mode is enabled by holding the ‘Esc’ and Down Arrow simultaneously
for a minimum of 15 seconds and releasing. Test mode times out after 30
minutes, and may also be ended by pressing ‘ESC’ and Up Arrow
simultaneously and releasing. Test Mode bypasses the On Delay (90 sec)
and Random Start timers for quicker troubleshooting. It also allows cycling
the reversing valve without compressor shutdown.