Appendix A : SPECIFICATIONS
Instrument
Operating Temperature Range
14°F to +122°F (-10°C to +50°C)
Battery
1.5V AA size (3)
Battery Life
> 6 Hours
Fuels
Natural Gas, LPG, Light Oil, Heavy Oil
OPT 1 (Bituminous Coal), OPT 2
(Anthracite Coal), OPT 3 (Coke), OPT 4
(Butane), OPT 5 (Wood), OPT 6
(Bagasse)
Display
Backlit LCD
Data Storage
50 sets of readings
Time & Date
24 Hour Real Time Clock
Dimensions
200mm x 90mm x 60mm
Weight
500g
Casing
Rubber Boot as Standard
Switch Off
Failsafe
Exhaust
Safety Spigot
Conforms to
BS7927 (and the draft BS7967)
Flue Temperature Probe
Construction
Pistol Grip with Stainless Steel Shaft
Hose Length
2500mm
Insertion Length
200mm
'K' Type Thermocouple Accuracy
+/- 0.3%, +/- 1°C
Maximum Temperature
800°C
Gases
Range
Resolution
Accuracy
Oxygen
0-25%
0.1%
+/- 0.3%
Carbon Monoxide
0-10,000 ppm
1 ppm
+/- 5 ppm or 5%
Whichever is greater
Carbon Dioxide
0-25%
0.1%
Calculated
CO/CO2 Ratio
0-0.999
0.001
Calculated
Combustion Efficiency
0-100%
0.1%
Calculated
9. PRINTING DATA
WARNING: - To operate correctly there must be a clear line of sight between
the Infrared Window on the instrument (see 3.3) and the Infrared Window on
the IR Printer (see Printer instructions). Place the printer so it is no closer
than approximately 6 inches from the analyzer.
1. Press the Print Key once
'rEAL' and “Stor’ will be displayed and ‘rEAL’ will be flashing.
Selecting ‘rEAL’ will cause the 708 to print the test data currently on the
display (real time data). Selecting ‘Stor’ will cause the 708 to print data
stored in memory. Use the Up and Down Arrow Keys to select the desired
print mode and press the Scroll/Enter Key.
REAL Print Mode - If rEAL print mode is selected, the analyzer will dis-
play ‘Wait’ ‘out’ and bars will change position on the LCD until printing is
complete.
After printing is complete, ‘End’ will be displayed and ‘YES’ (or ‘no’) will
blink. Selecting ‘YES’ will return the 708 to normal operation, selecting
‘no’ will return the 708 to the print selection screen so you can print
again. Use the Up and Down Arrow Keys to make the selection and press
the Scroll/Enter Key.
STOR Print Mode - If Stor mode is selected, 'Addr' will be displayed on
the top line along with 'SA ' and a location number from 0 to 9 will be
flashing on the screen. Select the required address location that you wish
to print data from by pressing the Up and Down Arrow Keys and press
the ‘Scroll/Enter’ Key. The analyzer will display ‘Wait’, ‘out’ and bars will
change position on the LCD until printing is complete.
After printing is complete, ‘End’ will be displayed and ‘YES’ (or ‘no’) will
blink. Selecting ‘YES’ will return the 708 to normal operation, selecting
‘no’ will return the 708 to the print selection screen so you can print
again. Use the Up and Down Arrow Keys to make the selection and press
the Scroll/Enter Key.
Combustion and pressure/draft printouts must be performed separately.
Perform a combustion test and save the data. Perform a pressure/draft
test and save the data in a different address. Print each address sepa-
rately.