6 user defined triggers, User defined triggers, User manual – SurgeX SX-AX20E User Manual
Page 18

© 2015 SurgeX/Electronic Systems Protection, Inc. | Technical Support: 800-645-9721 | surgex.com 18
User Manual
Firmware Version v2.04.281
5.5.6 User Defined Triggers
User defined triggers that have previously been
created are displayed in a list. The name of the
trigger is the name that was given to the trigger
when it was created. Pressing “Test Alarm” will
activate the trigger alarm action, and pressing
“Test Clear” will activate the trigger clear action;
use these test functions to verify that the trigger
will operate as intended.
Pressing “Edit” will open the trigger for editing,
and pressing “Delete” will delete the trigger. New
triggers may be created by pressing the “New
Trigger” button
Type
Trigger Executes When:
Trigger Clears When:
Threshold
Temperature High
Temperature > Set Point
Temp < Set - Hysteresis
Temperature Low
Temperature < Set Point
Temp > Set + Hysteresis
Voltage High
Voltage > Set Point
Voltage < Set – Hysteresis
Voltage Low
Voltage < Set Point
Voltage > Set + Hysteresis
Line Current High
Total Current > Set Point
Current < Set – Hysteresis
Line Current Low
Total Current < Set Point
Current > Set + Hysteresis
Outlet Current High
Outlet X Current > Set Point
Current < Set – Hysteresis
Outlet Current Low
Outlet X Current < Set Point
Current > Set + Hysteresis
Net Test
IP Address Ping Fails
IP Address Ping Succeeds
Schedule
Set Date and Time
NA
Contact Closure
Contact Closure Input Closes
Contact Closure Input Opens
Alarm/Clear Actions
Outlet On
Outlet Off
Outlet Reboot
Run Sequence
None