beautypg.com

Installation instructions, Isolated-circuit discrete input and output modules – Spectrum Controls 1746sc-OAP8I User Manual

Page 19

background image

Installation Instructions

Isolated-Circuit
Discrete Input and Output Modules

17

For IEC Type 1+ devices
that can't support 0.7 A
of inrush current, use an
external 500

1W

resistor on one input line
to reduce the inrush to
250 mA.

1746sc-IA8I

Isolated-Circuit 100/120 V ac/dc Inputs (8)

VAC/VDC
0+

VAC/VDC
1+

VAC/VDC
2+

VAC/VDC
3+

E-GND

VAC/VDC
4+

VAC/VDC
5+

VAC/VDC
6+

VAC/VDC
7+

IN 0–

IN 1–

IN 2–

IN 3–

E-GND

IN 4–

IN 5–

IN 6–

IN 7–

VS0 L2 or DC COM 0

VS0 L1 or +VDC

Alternative
input device
location

100/120 V ac/dc

VS1 L2 or DC COM 1

VS2 L2 or DC COM 2

VS3 L2 or DC COM 3

VS4 L2 or DC COM 4

VS5 L2 or DC COM 5

VS6 L2 or DC COM 6

VS7 L2 or DC COM 7

Rack mounting bolt

VS1 L1 or +VDC

VS2 L1 or +VDC

VS3 L1 or +VDC

VS4 L1 or +VDC

VS5 L1 or +VDC

VS6 L1 or +VDC

VS7 L1 or +VDC

Note -- The input circuits are electrically isolated from each other (the commons are NOT connected
internally). Therefore, up to eight different voltage sources (VS0-VS7) may be used.

Module ID Code = 303