beautypg.com

Environmental specifications – Spectrum Controls 2080sc-NTC User Manual

Page 24

background image

Micro800™ 4 Ch Universal Thermistor Input Module

24

Publication 0100198-01 Rev. A

Environmental Specifications

Environmental

Tests

Industry Standards

Test Level Limits

Temperature
(Operating)
(Performance
Criteria A)

IEC60068-2-1: (Test Ad,
Operating Cold),

IEC60068-2-2: (Test Bd,
Operating Dry Heat),

IEC60068-2-14: (Test
Nb, Operating Thermal
Shock)

-20° C to 65° C (-4° F
to 149° F)

Temperature

(Non-operating)
(Performance
Criteria B)

IEC60068-2-1:

(Test Ab, Unpackaged
Non-operating Cold),

IEC60068-2-2:

(Test Bb, Unpackaged
Non-operating Dry
Heat),

IEC60068-2-14:

(Test Na, Unpackaged
Non-operating Thermal
Shock)

-40° C to 85°C (-40°
F to 185° F)

Operating Altitude

2000 meters (6561 feet)

Not tested

Humidity
(Operating)
(Performance
Criteria A)

IEC60068-2-30:

(Test Db, Unpackaged
Damp Heat):

5 to 95% non-
condensing

Vibration
(Operating)
(Performance
Criteria A)

IEC60068-2-6: (Test Fc,
Operating)

5 g @ 10 to 500 Hz,
0.030 in. max. peak-
to-peak

Shock (Operating)
(Performance
Criteria A)

IEC60068-2-27: (Test
Ea, Unpackaged Shock)

30 g,11 ms half-sine
(3 mutually
perpendicular axes)

Shock (Non-
operating)
(Performance
Criteria B)

IEC60068-2-27: (Test
Ea, Unpackaged Shock)

50 g, 11 ms half-sine
(3 mutually
perpendicular axes)

Radiated Emissions CSIPR 11; Group 1,

Class A
FCC 47 CFR part 15
Class A

(Enclosure) Class A,
30 MHz

– 1 GHz