Analog Data (S1_Input_CH_n)

These registers display the current analog reading.

The following sample program, written in structured text, demonstrates
how to configure the module in CCW.

Controller.Micro830.Micro830.Main

(*********************************************)
(* FIRST TIME *)
(*********************************************)
FirstScanTimer(true, T#1ms);
IF (FirstScanTimer.Q = FALSE) THEN

FirstScan := FALSE;

CfgTimerEnable := FALSE;

CfgEnableWrite := FALSE;

S1_CFG_Trigger := 1;

previous_trigger := 0;

ReadModInfo(true, Slot_ID);

tmp_result := ANY_TO_DINT( ReadModInfo.ModRevision );

S1_STS_REV_MOD_0_MAJOR := ANY_TO_USINT( SHR( tmp_result, 8) );

S1_STS_REV_MOD_1_MINOR := ANY_TO_USINT( tmp_result );


(* Make sure it's cleared on the module *)

raw_config_array[0]

:= 0;

(* Low byte *)

raw_config_array[1]

:= 0;

(* High byte *)

END_IF;

DelayTimer(CfgTimerEnable, CFG_DELAY_TIME);

IF CfgTimerEnable = FALSE THEN

CfgTimerEnable := TRUE;

END_IF;


(*********************************************)
(* CONFIGURATION *)
(*********************************************)
IF (S1_CFG_Trigger = 0 AND

previous_trigger <> 0 AND

DelayTimer.Q = TRUE AND

WriteConfig.Sts = 1) THEN

CfgEnableWrite := TRUE;

previous_trigger := 0;

CfgTimerEnable := FALSE;

(* Reset timer *)

(* Make sure it's cleared on the module *)

raw_config_array[0]

:= 0;

(* Low byte *)

raw_config_array[1]

:= 0;

(* High byte *)

ELSIF (S1_CFG_Trigger <> 0 AND

previous_trigger = 0) THEN


CfgEnableWrite := TRUE;

previous_trigger := 1;

S1_CFG_Trigger := 0;

CfgTimerEnable := FALSE;

(* Reset timer *)

raw_config_array[0]

:= 255; (* Low byte *)

raw_config_array[1]

:= 255; (* High byte *)


idx := 2;