Electrical specifications – Spectrum Controls 2080sc-OW2IHC User Manual
Page 10

Micro800™ 2 Ch High Current Digital Output Module
10
Publication 0100188-01 Rev. A
The sample project on the previous page, can be downloaded from our
website at
http://www.spectrumcontrols.com/downloads.htm
Micro800™ 2 Ch High Current Digital Output Module
11
Publication 0100188-01 Rev. A
Electrical Specifications
Relay Output Specifications
Description
2 channel relay output module.
Relay
Functionality
Form A normally open
Output Current
Rating
(at rated
power)
Resistive load at up to 30° C
10A @ 5-30V dc
10A @ 125V ac
10A @ 250V ac
Resistive load at up to 65° C
6A @ 5-30V dc
6A @ 125V ac
6A @ 250V ac
Output Power
Rating
(Resistive
Resistive load at up to 30° C
300W Maximum for 30.0VDC
1250VA Maximum for 125VAC
2500VA Maximum for 250VAC
Inductive Loads
1
UL Pilot
Duty Contact
Ratings (Power
factor 0.35 or
less for AC):
Additional UL
ratings:
AC Contact Rating
Code Designation
Thermal
continuous test
current (A)
Max. current (A)
a,b
Max. VA
120 VAC
240VAC
Make
Break
Make
Break
Make
Break
B300
5
30 3 15 1.5
3600 360
Notes:
a
Power factor 0.35 or less
b
For maximum ratings at voltages between the maximum design value and 120 volts, the maximum
make and break ratings are to be obtained by dividing the volt-amperes rating by the application
voltage. For voltages below 120 volts, the maximum make current is to be the same as for 120 volts,
and the maximum break current is to be obtained by dividing the break volt-amperes by the application
voltage, but these currents are not to exceed the thermal continuous test current.
DC Contact
Rating Code
Designation
Thermal
continuous
test current
(A)
Max. make/break current (A)
c,d
Max. make / break
VA
125 VDC
250VDC
R150 1.0 0.22
-
28
R300 1.0 0.22 0.11
28
Notes:
c
The maximum make and break ratings are to be obtained by dividing the volt-ampere rating by the
application voltage, but the current values are not to exceed the thermal continuous test current.
d
Inductive loads as specified in Section 8.2.7 of Industrial Control and Systems; Control Circuit and Pilot
Devices, ANSI/NEMA
ICS5-1993.
1/3 hp, 125 V ac, 250V ac
30V dc Make / Break 2A (Pilot Duty)
250V ac, Make 20A / Break 2A (Pilot Duty)
2A, 250V ac, Tungsten Lamp
2A, 30V dc, Tungsten Lamp
1
Connecting surge suppressors across your external load will extend the life of the relay
contacts.