OPTI-UPS DS3000I User Manual

Page 30

background image

Rated Parameters Setting

26

DS-I 1-3k UPS User Manual

INPUT

OUTPUT

LOAD

MODE

CONVERTER

BYPASS

Current

mode

Current

votlage/frequency

6)

Protocol setting: press ON/OFF to choose mode and enter in protocol setting. Codes are

shown in LOAD, press FUNC to change protocol. First code: 0-Modbus, 1-SNT,

“CC”-current protocol.

INPUT

OUTPUT

LOAD

CONVERTER

BYPASS

Protocol

Current

setting

7)

Press ON/OFF to choose protocol and display current setting.

VAC

INPUT

OUTPUT

LOAD

MODE

CONVERTER

BYPASS

Hz

Current voltage

Current frequency

Current mode

Current protocol

8)

Press ON/OFF to save current setting and exit. If want to change, press FUNC and repeat

the procedures above.

9)

If you want to exit from setting mode and give up saving, press ON/OFF and FUNC

together for 2.5 seconds when in setting mode.

10) Restart and check if the setting is right.