Annex C. Rated Parameters Setting

Rated parameters of DS-I (L) 1-3K UPS can be set from panel. Please set rated parameters in

according to the following procedures:

1)

Start UPS power supply and ensure that rectifier, inverter, bypass and discharge are not

working.

2)

Press ON/OFF and FUNC together for 2.5 seconds to enter in setting mode, all LEDs

flicker.

3)

Voltage setting: press FUNC to change rated voltage. Shown as following:

VAC

INPUT

VAC

OUTPUT

CONVERTER

BYPASS

LOAD

Current Rated

Voltage

4)

Frequency setting: Press ON/OFF to choose voltage and enter in frequency setting. Press

FUNC to change rated frequency. Shown as following:

INPUT

OUTPUT

LOAD

CONVERTER

BYPASS

Current Rated

Frequency

Hz

Hz

5)

Mode setting: press ON/OFF to choose frequency and enter in mode setting, press FUNC

to change mode. First code: n-normal mode, E-ECO mode. Second code indicated

current voltage/frequency are listed in description of main menu in section 6.