12. Technical specifications

Input Characteristics

Capacity:

Voltage Range:

Phases:

Frequency Range:

Termination

terminal block

30 KVA

380Y/220 Volt, +15% to - 15% at 50 Hz for regulation.

Three phases-4 wire ,Wye connection(R,S,T,N,G)

47-53Hz for 50Hz models +/-3Hz

terminal board

Output Characteristics

Voltage:

Phases:

Voltage Range:

Frequency Range:

Load Regulation:

Harmonic Distortion:

Efficiency:

Overload:

Wav e form:

Insulation Resistance:

Technology:

By-pass Switch

Cooling:

Termination

380Y/220 Volt

Three phases-4 wire ,Wye connection(U,V,W,N,G)

Regulated to ±1~2% of nominal voltage with an input voltage range of +15

to –15%

50Hz, for every 1% change in input frequency the output voltage will

change by 1% in the same direction.

5%, no load to full load

non

97% at full load.

For 1 minutes 100%,for 30 minutes 125%,for 60 minutes 100%.

Sinewave

5 megaohms from winding to core measured at 500Vdc

This technique usesthe combination of a motor driven variable transformer

with buck-boost transformer technology.

input power directly to load, bypassing the voltage regulator.

fan assisted

terminal board

Environmental

Audible Noise:

Ambient Temperature:

Operating Altitude:

Operating Humidity:

Heat Rejection:

Less than 65 dBA at 1.5 metre

0° to 40 °C Operating,

10° to 90 °C Storage

3,000 metre without derating

90% relative (non-condensing)

At full load, 10% of VA rating x 3.41.

13- Machine schematic view/outline