Operation examples, Setup of pv input range type, Setup of event operation type – Nor-Cal SDC15 Controller User Manual
Page 3: Execution of auto tuning (at), Setup of sp value, Green letters, Blue letters

5
4
Operation examples
Setup of
PV input range type
Start from the
operation display
(if necessary 
press [mode] once 
to get the opera-
tion display).
Press and hold
[para] for more
than 2s to get the
parameter setup 
display. 
a--M
is
shown on the 
upper display.
Press and hold
[para] for more
than 2s again to
get the setup
setting display.
The current set
value for 
C0 1
(PV input range
type) is displayed.
When the [<], [ ]
or [ ] key is
pressed, the right-
most digit on the
lower display
flashes. If no key
is pressed for 
more than 2s after 
changing to the 
desired value in 
the PV input range 
list, the display 
changes from 
flashing to conti-
nuously lit, and 
the displayed 
value is now set.
<
<
If no sensor is connected, 
an alarm for abnormal 
PV input (any one from
AL0 1
to
AL 1 1
) may
appear on the upper
display.
In case of ON/OFF 
control, 
r--r
appears
on the upper display.
Setup of
event operation type
Start from the 
operation display
(if necessary 
press [mode] 
once to get the
operation display).
Press and hold
[para] for more
than 2s to get the
parameter setup
display. 
a--M
is
shown on the
upper display.
Press and hold
[para] for more
than 2s again to
get the setup
setting display.
The current set
value for 
C0 1
(PV input range
type) is displayed.
Press [para] 
repeatedly to get
e 1.c 1
on the upper
display.
0
is
displayed on the 
lower display.
In this example, the event 1 operation type is set to
deviation high limit.
Similarly, use e2.C 1 to set the event 2 operation type, and 
use e3.C 1 for event 3.
When the [ ] or [ ] key is pressed, the rightmost
digit on the lower display flashes. Change the
flashing digit to 
4
by pressing [ ] or [ ].
If no key is pressed for more than 2s, the 
displayed value is set and the display changes 
from flashing to continuously lit. 
<
<
<
<
4
on the lower display indicates that the event operation type is
set for deviation high limit.
0
on the lower display
indicates that the event 
operation type is set to 
"none."
Execution of
auto tuning
(AT)
Start from the 
operation display 
(if necessary 
press [mode] 
once to get the 
operation display).
Press and hold 
[para] for more 
than 2s to get the 
parameter setup 
display. 
a--M
is
shown on the 
upper display.
Press [para] twice. 
The upper display 
says 
at
and the
lower display says
at.Of
.
When [ ] or [ ] is 
pressed, 
at.Of
flashes.
If no key is pressed 
for more than 2s,
at.ON
remains steadi-
ly lit and AT begins. 
During AT, the right-
most decimal point
flashes twice re-
peatedly. (When AT
is done, the light 
goes off and the 
new PID values go
into effect.)
Press [ ] once.
The lower display 
starts to flash
at.On
.
AT forces ON/OFF of the MV a number of times (a limit 
cycle) to calculate PID values.
Check that this operation does not create any problems 
for the associated equipment before executing AT. 
During the AT process, if the mode is changed to 
READY or MANUAL, if PV input is faulty, or if a power 
failure occurs, AT stops automatically without changing 
the PID values.
AT can also be stopped by changing the setting from
At.ON
to
At.OF
(return to step 3 above).
<
<
<
If the control method is 
ON/OFF control and if 
Bit 3 (AT stop/start 
display) of the mode 
display setting (C73) is 
set to "disabled: 0," 
nothing is displayed.
Flashing occurs only in 
RUN and AUTO modes, 
if there is no PV input 
abnormality. 
Also, if "AT stop/start" is 
selected for DI assign-
ment, the display does 
not blink and no change 
can be made.
Setup of
SP value
Start from the 
operation display 
(if necessary 
press [mode] once 
to get the opera-
tion display).
Check that the 
operation display 
is displaying the 
SP. 
(If not, press [para] 
repeatedly until the 
SP is displayed.)
When the [<], [ ] 
or [ ] key is press-
ed, the rightmost 
digit on the lower 
display flashes and 
the SP can be 
changed to the 
desired value.
In this case, the 
flashing of the 
numerical value 
implies that it is not 
yet set. A numerical 
setting that is being 
changed flashes 
the same way.
If no key is pressed 
for more than 2s, 
the displayed value 
is set and the 
display changes 
from flashing to 
continuously lit.
<
<
If the [mode] key is 
pressed when the 
display is flashing, the 
status returns to that of
step 1. 
If an SP limit is in effect, the numerical 
value cannot be changed to a value 
above the limit. The SP limit must be 
changed first.
Green letters
: Items before operation
Blue letters
: Items during operation
Start from the 
operation display 
(if necessary press 
[mode] once to get 
the operation 
display).
Press and hold 
[para] for more 
than 2s to get the 
parameter setup 
display. 
a--M
is
shown on the 
upper display.
Press the [para] 
key once. The 
upper display says 
r--r
and the lower
display says
rdy
(or
run
).
When [ ] or [ ] is 
pressed, the lower 
display flashes.
If no key is pressed 
for more than 2s, 
the displayed value 
is set and the 
display changes 
from flashing to 
continuously lit.
When [ ] or [ ] is 
pressed, 
run
(or
rdy
) on the lower
display flashes.
>
>
>
>
The current mode is 
indicated by 
run
for
RUN mode or
rdy
for
READY mode.
In case of ON/OFF 
control, 
r--r
appears
on the upper display.
If the DI assignment is 
set to "RUN/READY 
selection," the display 
does not flash and no 
change can be made.
RUN/READY
mode selection
Setup of
PID value
Setup of
event value
Start from the 
operation display 
(if necessary press 
[mode] once to 
get the operation 
display).
Press and hold 
[para] for more 
than 2s to get the 
parameter setup 
display. 
a--M
is
shown on the 
upper display.
Press [para] 
repeatedly to get
p-1
(for propor-
tional band) on 
the upper display. 
The value set for
p-1
is displayed on
the lower display.
When [<], [ ] or 
[ ] is pressed, the 
rightmost digit on 
the lower display 
flashes, and can 
be changed to the 
desired value for 
the proportional 
band. 
In this case, the 
flashing of the 
numerical value 
implies that it is 
not yet set. A 
numerical setting 
that is being 
changed flashes 
the same way.
Similarly, use
i-1
to set the integral time (0 to 9999s),
and
d-1
to set the derivative time (0 to 9999s).
>
>
If the control method is 
"ON/OFF control," 
nothing is displayed.
The proportional band 
can be set in a range 
from 0.1 to 999.9%. 
If no key is pressed for more than 2s, the 
displayed value is set and the display changes 
from flashing to continuously lit.
If the [mode] key is pressed when the display is flashing, the status 
returns to that of step 1.
Start from the 
operation display 
(if necessary press 
[mode] once to get
the operation 
display). 
Press and hold 
[para] for more
than 2s to get the 
parameter setup 
display. 
a--M
is
shown on the 
upper display.
Press [para] 
repeatedly to get
e 1
on the upper
display. The lower 
display says 
0
.
When [<], [ ] or 
[ ] is pressed, the 
rightmost digit on 
the lower display 
flashes, and can 
be changed to the 
desired value for 
the event. 
In this case, the 
flashing of the 
numerical value 
implies that it is 
not yet set. 
A numerical set- 
ting that is being 
changed flashes 
the same way.
To set hysteresis 
as well, press 
[para] once (or 
twice, depending 
on the settings) to 
display 
e 1.hy
on
the upper display. 
The lower display 
says 
5
.
When [<], [ ] or 
[ ] is pressed, the 
rightmost digit on 
the lower display 
flashes, and can 
be changed to the 
desired value for 
hysteresis.
If no key is pressed 
for more than 2s, 
the displayed value 
is set and the 
display changes 
from flashing to 
continuously lit.
Similarly, use
e2
to set a value for event 2, and
e3
to set
a value for event 3.
Similarly, use
e2 hy
to set a hysteresis value for event 2,
and
e3 hy
to set a hysteresis value for event 3.
>
>
<
<
0
on the lower display
indicates that the event 
main set value is "zero."
5
on the lower display
indicates that the current 
set value for event 
hysteresis is 5.
If no key is pressed for more than 2s, the displayed 
value is set and the display changes from flashing 
to continuously lit.
If the [mode] key is pressed when the display is flashing, the status 
returns to that of step 1.
Memo
• For step numbers indicated in red like
, the following precaution applies:
If the key lock is set, the numerical value does not flash, and the value cannot be changed.
To change a numerical value, cancel the key lock first.
