INSTALLATION

Continued

Figure 16 - Checking Gas Joints for

Propane/LP Gas

Figure 14 - Equipment Shutoff Valve

Propane/LP
Supply Tank

Open

Closed

Equipment
Shutoff Valve

Figure 15 - Checking Gas Joints for

Natural Gas

Equipment
Shutoff
Valve

Gas
Meter

Thermostat Gas Valve
(Inside Heater)

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 14).
2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

3. Check all joints from gas meter for natural gas

(see Figure 15) or propane/LP supply tank for

propane/LP gas, to equipment shutoff valve

(see Figure 16). Apply a noncorrosive leak

detection fluid to all joints. Bubbles forming

show a leak.

4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 14).
2. For natural gas open main gas valve located

on or near gas meter. For propane/LP gas open

propane/LP supply tank valve.

3. Make sure control knob of heater is in the OFF

position.

4. Check all joints from equipment shutoff valve

to thermostat gas valve (see Figure 15 or 16).

Apply a noncorrosive leak detection fluid to

all joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Light heater (see Operating Heater, page 13).

Check all other internal joints for leaks.

7. Turn off heater (see To Turn Off Gas to Appli-

ance, page 14).

8. Replace front panel.

Equipment
Shutoff
Valve

Thermostat Gas Valve
(Inside Heater)