beautypg.com

Grounding, D series lake quick start guide rev 1.2.0, Split phase 200v – Lab.gruppen D Series 80:4L User Manual

Page 11

background image

10. Grounding

D SERIES Lake Quick Start Guide rev 1.2.0

11

Connecting the amplifier in three phase delta configuration
In three-phase configuration where the phases are 120 degrees apart, one can connect three balanced loads in a
delta configuration. The connection is made between the phases instead of between the neutral and a phase.

Amp

120V

120V

120V

L1

Amp

L2

L3

Amp

N

N

Amp

Amp

Amp

3 phase Y 120V

3 phase delta 208V

208V

208V

208V

L1

L2

L3

Three phase delta configuration

Connecting the amplifier in a split phase configuration
In two phase split-phase configuration there are two phases separated by 180 degrees. Connecting between the
phases gives double the line voltage.

Two phase split-phase configuration

10. Grounding

Use correctly-shielded balanced audio input connections to minimize hum and interference.

D Series must be grounded (earthed) with the safety ground pin to the mains distribution system.
NEVER disconnect the earth (ground) pin on the mains cable (AC power cord).

Split phase 100V

100V

100V

200V

L1

Amp

L2

N

Amp

Split phase 200V

L1

L2

N

Amp

This manual is related to the following products: