beautypg.com

9 fault finding – Glow-worm Ultimate 40CF User Manual

Page 18

background image

18

221785B

9 Fault Finding

Re-connect boiler flue blockage
safety device to points A and B.
Disconnect thermocouple at
connection point D of the gas valve.
Test continuity between point C and the
body of the gas valve.
Is there continuity?

Test continuity of thermocouple between inner
connection point D and point E.
Is there continuity?

Faulty boiler flue blockage
safety device, renew.

Thermocouple and boiler flue blockage
safety device circuit satisfactory.

NO

YES

YES

Faulty flue blockage safety device
connectors into gas valve,
either at A or C.
Renew where faulty.

Faulty thermocouple, renew.

With the boiler cold, check connections of the thermocouple, boiler flue blockage safety device
and gas valve. Reset flue blockage safety device.
Disconnect flue blockage safety device connectors at points A and B at the gas valve,
see diagram Interrupter Electrical Connections.
Test continuity of the flue blockage safety device. Is there continuity?

YES

NO

NO

PERMANENT
LIVE
230V
50Hz

3A FUSE

THERMOSTAT

L

RED

C

NC

BROWN

MULTI-FUNCTIONAL

CONTROL

SOLENOID

BLUE

N

3

4

Diagram 9.3

FUNCTIONAL FLOW WIRING

2327/B

Diagram 9.2

THERMOCOUPLE FAULT FINDING

9.1 Pilot

Refer to chart 9.1.

9.2 Thermocouple

Refer to chart and diagram 9.2.

9.3 Electrical

Refer to diagram 9.3 and 9.4.

The preliminary electrical system checks as contained in a
multimeter instruction book are the first checks to be carried out
during fault finding.

On completion of any fault finding task which has required the
breaking and remaking of electrical connections then the checks,
earth continuity, polarity and resistance to earth, must be
repeated.

9.4 Flue Blockage Safety Device

If the device operates it indicates there is a problem with the
chimney. Make sure that the air vents are free from obstruction.
Carryout spillage checks as Section 2.3.

9008