beautypg.com

Installation – Glow-worm Betacom2 User Manual

Page 20

background image

0020145065_01 - 09/12 - Glow-worm

10.2 Main board

1

2

3

30mm

max

Key

1 Connector

2 Electrical wires

3 Insulation

• Keep a distance of a maximum of 30 mm between connector

(1) and the start of the insulation (3).

• Fix the cables in the cable-clamp on the eBox.

10.3 Electrical wiring

Connection of the whole electrical system and any heating system

controls to the electrical supply must be through a double poled

common switched and fused isolator.

The isolator shall have a contact separation of 3mm on each pole.

It should be identified as to its use. Wiring to the boiler must be

PVC 850C insulated cable not less than 0.75mm² (24/0.20).

A fused three pin plug and shuttered socket outlet may be used

instead of a fused spur box provided that it is not used in a room

containing a fixed bath or shower.

24

V

1

Key

1 Power supply cable

• Connect the appliance's power cable to the 230 V single-phase

network + earth.

• Observe correct polarity when connecting the appliance.

10.3.1

230V permanent supply

a

DANGER:

All cables connected to the appliance should be

permanently fixed to the wall.

i

IMPORTANT:

This appliance will not operate without a link or system

controls fitted.

24

V

3

4

1

2

Key

1 230V permanent supply

2 Main board terminal block

= Mains earth

N = Mains neutral

L = Mains live

3 fuse

4 Double pole connector

• Connect mains supply as described.

INSTALLATION

- 18 -