Warning – Dunkirk DXL Series User Manual

Page 5

background image

5

1.

Installation must conform to requirements of authority

having jurisdiction or, in absence of such requirements,

to the National Fuel Gas Code, ANSI Z223.1/NFPA 54.

2.

Where required by authority having jurisdiction,

installation must conform to the Standard for Controls

and Safety Devices for Automatically fi red Boilers,

ANSI/ASME CSD-1.

3.

Boiler series is classifi ed as Category I. Vent

installation shall be in accordance with "Venting of

Equipment ," of the National Fuel Gas Code, ANSI

Z223.1/NFPA 54, or applicable provisions of local

building codes.

4.

Boiler has met safe lighting and other performance

criteria with gas manifold and control assembly on

boiler per latest revision of ANSI Z21.13/CGA 4.9.

5.

Boiler shall be installed such that gas ignition system

components are protected from water (dripping,

spraying, rain, etc.) during appliance operation and

service, (circulator replacement, condensate trap,

control replacement, etc.).

6.

Locate boiler on level, solid base as near chimney as

possible and centrally located with respect to heat

distribution system as practical.

7.

Allow 24 inches (610mm) at front and right side for

servicing and cleaning.

8.

When installed in utility room, door should be wide

enough to allow largest boiler part to enter, or to

permit replacement of another appliance such as water

heater.

9.

FOR INSTALLATION ON NON-COMBUSTIBLE

FLOORS ONLY - For installation on combustible

fl ooring special base must be used. (See Replacement

Parts Section.) Boiler can not be installed on

carpeting. Minimum clearances to combustible

construction are:

TOP ....................................18 IN. (457mm)

FRONT .........................................ALCOVE *

FLUE CONNECTOR ................. 6 IN. (152mm)

REAR ................................... 4 IN. (102mm)

CONTROL SIDE ..................... 9 IN. (229mm)

OTHER SIDE ........................... 3 IN. (76mm)

HOT WATER PIPING ................ Per Local Code

NOTE: Greater clearances for access should supersede fire

protection clearances.

* Defi nition of Alcove is three sided space with no wall in

front of boiler. ANSI standard for alcove is 18 inches from

front of appliance to leading edge of side walls as shown

below.

4 - INSTALLATION PROCEDURE

WARNING

Improper installation, adjustment, alteration, service

or maintenance could result in death or serious

injury

.

!

WARNING

Fire hazard. Do not install boiler on combustible

fl ooring or carpeting. Failure to follow these

instructions could result in death or serious injury.

!

Minimum Clearances to Combustible

Construction (as seen from above)

Figure 2 - Clearance to Combustibles

3"

4"

BOILER

18"

9"

Front