17 - OPERATING THE BOILER - SETTING THE CONTROL

Wiring An Indirect Water Heater
When installing with indirect water heater, signal from

indirect must be separated from heating zone signals and

wired appropriately.
If you choose not to separate indirect signal from heating

zones, Economy Feature should be turned off to insure

boiler supplies adequate temperature to heat the indirect

tank.

Setting The Control
Settings can be checked using the TEST/SETTINGS Button.

See page 23 for details.

Setting The High Limit
The high limit is factory set at 190°F. To adjust, turn

HI TEMP dial A until desired setting is displayed.

(Setting range: 130°F - 220°F)

Setting The Low Limit
Low limit is designed to maintain temperature in boiler

suitable for domestic hot water. Low limit is factory set to

OFF. Prior to adjusting, remove the jumper (not equipped

on all units) B.
Then turn LO Temp dial C clockwise until desired

temperature is displayed. For Proper operation, low

temperature limit setting should be at least 10° below high

limit setting. For cold start operation, low limit must be

turned OFF. If low limit temperature cannot be set above

140°F, remove jumper B. (Setting range: OFF or 110°-

200°F).

Setting The Economy Feature
Economy Feature is factory set for 1 zone heating

system. To adjust, turn the ECONOMY dial D until the

number displayed equals the number of heating zones.

The Economy Feature conserves fuel by reducing boiler

temperature. If heating system is unable to supply needed

heat to the house, Economy dial should be turned to lower

setting (example: In a three zone house, turn dial to 2 or

1). Conversely, if boiler provides adequate heat, added

fuel savings can be achieved by selecting a higher setting

(example: 4 or 5). If heating and indirect water heater

signals were not separated when wiring control, Economy

Feature should be turned OFF to insure boiler supplies

adequate temperature to heat the indirect tank.

SETTING

OFF

Disables economy function. Will allow boiler to fi re
until hi-limit temp is reached and re-fi re with a 10°
subtractive differential.

LO

Provides lowest level of fuel savings. Use this set-
ting only if the house does not stay warm at higher
settings.

1

Recommended setting for single zone systems.

2

Recommended setting for Two zone systems.

3

Recommended setting for Three zone systems.

4

Recommended setting for Four zone systems.

5

Recommended setting for Five zone systems.

HI

Provides highest level of fuel savings.

Activation Thermal Pre-Purge (Optional)
Activation of this feature is not recommended for boiler

supplying domestic hot water.
Fuel Smart HydroStat has a Thermal Pre-Purge feature to

maximize effi ciency. When activated, control will purge

higher boiler temperatures down to 135°F at start of any

thermostat call and supply the latent energy in the boiler

to the heating zone that is calling. During the purge cycle,

the display will indicate Pur. If the heat is not suffi cient to

satisfy the thermostat, control will energize burner. Feature

works with single and multi-zone heating systems utilizing

circulators or zone valves. No change in wiring is needed.
To Activate Thermal Pre-Purge
Push and hold the TEST/SETTINGS button for 20 seconds.

Display will read Pur On. To deactivate this feature, push

and hold button a second time for 20 seconds. Display will

read Pur OFF.

Decimal Point

(Indicates heat call)

High

Temperature

Limit Setting

(130°-220°F)

Factory 190°F

Economy Dial

(OFF or LO,

1,2,3,4,5,HI)

Jumper

B

Dynamic Display

Water

Temperature

and Real Time

Verifi cation

of Setting

Adjustments.

Differentials

are automatic

and will vary

based on

control settings

and boiler

temperature

Low

Temperature

Limit Setting

(OFF or 110°-

200°F) Factory

Off

Diagnostic LEDs

and Test Buttton