Warning – Dunkirk DXL Series User Manual
Page 19

19
Thermostat actuates on call for heat,
completing circuit to control. Completed
circuit to control will fi rst activate circulator
and damper which will close end switch inside
damper. Completes circuit to ignition system,
ignition takes place.
In event boiler water temperature exceeds
high limit setting on boiler mounted high limit
control, power is interrupted between control
system and ignition system. Power remains
off until boiler water temperature drops below
high limit setting. Circulator continues to
operate under this condition until thermostat is
satisfi ed.
In event fl ow of combustion products through
boiler venting system becomes blocked, blocked
vent safety switch shuts main burner gas off.
Similarly, if boiler fl ue-way becomes blocked,
fl ame rollout safety switch shuts main burner
gas off. See Figure 17 . If either of these
conditions occur, do not attempt to place boiler
back into operation. Contact certifi ed service
agency.
Before seasonal start-up, have a certifi ed service agency
check boiler for soot and scale in fl ues, clean burners and
check gas input rate to maintain high operating effi ciency.
WARNING
Label all wires prior to disconnection when servicing
controls. Wiring errors could cause improper and
dangerous operation.
!
Verify proper operation after servicing
Service agency will verify system is fi lled with water to
minimum pressure and open air vents, if used, to expel any
air accumulated in the system. Check entire piping system
and, if any leaks appear, have them repaired.
Circulators need to be checked and maintained.
Refer to circulator manufacturer's instructions.
Inspect venting system at the start of each heating
season. Check vent pipe from boiler to chimney for signs of
deterioration by rust or sagging joints. Repair if necessary.
Remove vent pipe at base of chimney or fl ue and using a
mirror, check vent for obstruction and verify vent is in good
working order.
Boiler fl ue gas passageways may be inspected by a light
and mirror. Remove burner door. See Figure 20, Page 20 .
Place trouble lamp in fl ue collector through draft relief
opening. With mirror positioned above burners, fl ue gas
passageways can be checked for soot or scale.
This procedure should be followed to clean fl ue gas
passageways:
1.
Remove burners from combustion chamber by raising
burners up from manifold orifi ces and pulling toward
front of boiler. See Figure 17 .
2.
Disconnect vent pipe from draft hood.
3.
Remove top jacket panel.
4.
Remove combination fl ue collector and draft hood from
boiler castings by loosening nuts on hold down bolts
located on each side of collector. See Figure 17 .
5.
Place sheet of heavy paper or similar material over
bottom of base and brush down fl ue passageways. Soot
and scale will collect on paper and is easily removed
with the paper.
6.
With paper still in place in base, clean top of boiler
castings of boiler putty or silicone used to seal between
castings and fl ue collector. Verify chips are not lodged
in fl ue passageways.
When cleaning process is complete, restore boiler
components to their original position. Use IS-808 GE
silicone (available from distributor) to seal around fl ue
collector and boiler castings.
14 - SEQUENCE OF OPERATION
15 - GENERAL INSTRUCTIONS
Blocked Vent
Safety Switch
Rollout Switch
4 Section Boiler
Rollout Switch
2,3,5
Section Boiler
Integral Draft
Hood
Base
Burner
Door
Burners
Orifi ces
Jacket Base
Panel
Manifold
Figure 17 - Blocked Vent Safety Switch, Roll-
out Safety Switch