Dunkirk Helix VLT Vertical Laser Tube, Wall Hung Modulating Condensing Boiler User Manual

Page 6

background image

6

A6. Set The Stainless Condensing Boiler CH

6-1. Set stainless Condensing boiler to be Master boiler

in Cascade mode. Change S4-switch to ON posi-

tion, (away from S4 mark on control board). See

Figure A5.

6-2. Change boiler address to Cascade 1 following

procedure below.
• Press down and hold “Enter” button and

immediately press down and hold “Menu” button

for 5 seconds to enter into Installer Menu.

• Use arrow keys to go to “Boiler Config”
• Press “Enter” key
• Press “Enter” key again. The number after

“Boiler Address:” will be flashing.

• Use arrow keys to change this number to 1.
• Press “Enter” key, number will stop flashing.
• Press “Menu” key twice to exit Installer Menu.
• CASCADE 1 should appear on user interface.

6-3a Set System Temperature Setting for Stainless

Condensing boiler. If outdoor reset is activated

(CH Mode 1 or CH Mode 2) and if heating system

requires a reset curve different from the default

curve.
• Change Outdoor Reset curve. Detailed

instructions can be found in boiler Installation,

Operation and Maintenance Manual (IOM).

• Set “Boiler Max” parameter to about 20°F lower

than setting point of Additional Heating Device,

i.e. 150°F.

6-3b If outdoor reset function is deactivated (CH

mode 0), follow procedure below to set System

Temperature Setting point.

• Press “Menu” button.
• Scroll down to “Setting” using arrow keys.
• Press “Enter” key.
• Press “Enter” key again. The number after

“Cascade CH Setting” will be flashing.

• Use arrow keys to change this number to about

20°F lower than setting point of Additional

Heating Device, i.e. 150°F.

• Press “Enter” key. Number will stop flashing.
• Press “Menu” key twice to exit setting mode.

A7. Set The Stainless Condensing Boiler DHW Setting

7-1 Set DHW supply temperature setting of stainless

condensing boiler to temperature about 10°F lower

than corresponding DHW setting point on Additional

Heating Device, i.e. 170°F.

A8. Create CH call for heat and verify system works

as intended.

A9. Create DHW call for heat, if applicable, and verify

system works as intended.

SECTION A - STAINLESS CONDENSING BOILER OPERATING WITH HIGH TEMPERATURE HEATING DEVICE