BACKGROUND

Application Concept

I. Kit is for applications that employ ECR Stainless Condensing

boiler to work with an additional heating device.

II. If the additional heating device can constantly supply

hot water at 165°F or HIGHER, it is considered a HIGH

Temperature Heating Device. Follow installation procedure

in SECTION A. Following are common High Temperature

Heating Devices

• Indoor wood water boiler
• Outdoor wood water boiler
• Electric boiler

III. If Additional Heating Device only constantly supplies

hot water at LESS THAN 165°F, it is considered a LOW

Temperature Heating Device. Follow installation procedure

in SECTION B. Following are common Low Temperature

Heating Devices.

• Geothermal hot water heating device

• Solar water heating device

• Electric hot water heat pump

IV. Heating capacity of the additional heating device will be fully

utilized when available.

V. Stainless Condensing boiler will fire only when the additional

heating device cannot satisfy heat demand.

Water Flow Arrangement

VI. The piping connection establishes flow where water flows

through the two heating devices (Stainless Condensing boiler

and Additional Heating Device) in a sequential manner. The

goal is to make the two heating units work together at the

maximum possible system heating efficiency.
If the additional heating device is a HIGH temperature device,

return water goes into the Stainless Condensing boiler first.

The purpose is to have the stainless condensing boiler work in

the condensing regime as much as possible. SECTION A.
If the additional heating device is a LOW temperature heating

device, return water flows into additional heating device first

to fully utilize the capacity of the additional heating device.

SECTION B.

VII. The water flow arrangement takes advantage of the Stainless

Steel Condensing boiler's built in primary loop and internal

water pump.

Water Temperature Control

VIII. The system is configured so the Stainless Condensing boiler

control system will modulate its firing rate to sustain Supply

Water Temperature at the setting point in all conditions.

• When Additional Heating Device is supplying heat at

its full capacity.

• When Additional Heating Device is supplying heat at

reduced capacity.

• When Additional Heating Device is not supplying

heat.

Heating Priority Establishment

IX. The two heating units are configured to supply heat in the

following manner.

• When the Additional Heating Device alone CANNOT

maintain supply water temperature at or higher

than the temperature set point of the Stainless

Condensing boiler, the Stainless Condensing boiler

will fire.

• When the Additional Heating Device alone CAN

maintain a supply water temperature higher

than the temperature set point of the Stainless

Condensing boiler, the Stainless Condensing boiler

will NOT fire.

BACKGROUND