Fuel piping – Delta F-25 User Manual
Page 34
29
Fuel Piping
Pipe Sizing - Natural Gas
1. Refer to Table 1 for pipe length and diame-
ter requirements. Based on rated ELITE
input (divide by 1,000 to obtain cubic feet
per hour).
-
Table 1 is based on Natural Gas with a
specific gravity of 0.60 and a pressure
drop through the gas piping of
0.30”w.c..
- For additional gas piping sizing infor-
mation, refer to ANSI Z223.1. For
Canadian installations refer to B149.1
or B149.2.
Natural Gas Supply Pressure Requirements
1. Pressure required at the gas valve inlet
supply pressure port:
-
Maximum 13”w.c. at flow or no flow
conditions to the burner.
-
Minimum 5”w.c. during flow condi-
tions to the burner. Must be verified
during start up.
2. Install 100% lockup gas pressure regulator
in the gas supply line if inlet pressure can
exceed 13”w.c at any time. Adjust the lock-
up pressure regulator for 13”w.c maximum.
Pipe Sizing - Propane Gas
1. Contact the local propane gas supplier for
recommended sizing of piping, tanks and
100% lockup gas regulator.
Propane Gas Supply Pressure Requirements
1. Adjust the propane supply regulator pro-
vided by the gas supplier for 13”w.c. max-
imum pressure
2. Pressure required at the gas valve inlet sup-
ply pressure port:
-
Maximum 13”w.c. at flow or no flow
conditions to the burner
-
Minimum 5”w.c. during flow condi-
tions to the burner. Must be verified
during start up.
Length of Pipe
in Feet
SCH 40
1/2"
3/4"
1"
1-1/4"
1-1/2"
10
132
278
520
1050
1600
20
92
190
350
730
1100
30
73
152
285
590
860
40
63
130
245
500
760
50
56
115
215
440
670
75
45
93
175
360
545
100
38
79
150
305
460
150
31
64
120
250
380
Capacity of Pipe in Cubic Feet of Gas Per Hour
(based on 0.60 specific gravity, 0.30" w.c. pressure drop)
Table 1: Gas piping sizing - Natural Gas