CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply a noncorrosive leak detec-

tion fluid to all joints. Bubbles

forming show a leak. Correct all

leaks at once.

CAUTION: Make sure exter-

nal regulator has been installed

between propane/LP supply

and heater. See guidelines un-

der Connecting to Gas Supply,

page 14.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)

1. Disconnect appliance with its appliance main

gas valve (control valve) and equipment

shutoff valve from gas supply piping system.

Pressures in excess of 1/2 psig will damage

heater regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

4. Check all joints of gas supply piping system.

Apply noncorrosive leak detection fluid to all

joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Reconnect heater and equipment shutoff valve

to gas supply. Check reconnected fittings for

leaks.

Test Pressures Equal To or Less Than 1/2
PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Figure 17).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

3. Check all joints from gas meter to equipment

shutoff valve for natural gas or propane/LP

supply to equipment shutoff valve for pro-

pane/LP (see Figure 18 or 19, page 17). Apply

noncorrosive leak detection fluid to all joints.

Bubbles forming show a leak.

4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS
CONNECTIONS

1. Open equipment shutoff valve (see Figure 17).

2. Open main gas valve located on or near gas

meter for natural gas or open propane/LP

supply tank valve.

3. Make sure control knob of heater is in the OFF

position.

4. Check all joints from equipment shutoff valve

to thermostat gas valve (Thermostat-Con-

trolled Models) or to gas control (Remote-

Ready Models) (see Figure 18 or 19, page

17). Apply noncorrosive leak detection fluid

to all joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Light heater (see Operating Heater, page 20

or 22, depending on your model). Check all

other internal joints for leaks.

7. Turn off heater (see To Turn Off Gas to Appli-

ance, page 21 for Thermostat-Controlled mod-

els or page 23 for Remote-Ready Models).

Figure 17 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff
Valve