Vent terminal, roof installation, Optional blower installation – Drolet Ultra Flame DG05437/DG05447 User Manual

Page 21

background image

ULTRA FLAME DV “0” Clearance Fireplace

VENT TERMINAL, ROOF INSTALLATION

Roof vents are required to extend at least 3 ft. above the highest point where they pass through
the roof of the building and at least 2 ft. higher than any portion within 10 feet.


• Clearance between combustible wall and vent pipe must be 2" and a radiation shield must be

used through the insulated wall.


• If the vent terminal is more than 5 feet above the roof, use roof braces to secure the whole

assembly.

OPTIONAL BLOWER INSTALLATION


See the instruction sheet included with the optional blower before proceeding with its

installation.

21