9

CONTROL BOX
AND COMPRESSOR
ACCESS DOOR

OUTDOOR AIR
SCREEN

FILTER ACCESS DOOR

GAS SECTION
ACCESS DOOR

INDOOR MOTOR
ACCESS DOOR

CONDENSER COIL

ACCESS DOOR

C08545

Fig. 6 -- Panel and Filter Locations (48PG03--07 Shown)

MAINTAINING YOUR UNIT

All maintenance should be handled by skilled, experienced
personnel. Your dealer can help you establish a standard procedure.
For your safety, keep the area around the unit clear and free of
combustible materials, gasoline and other flammable liquids and

vapors.
To assure proper functioning of the unit, flow of combustion and
ventilating air must not be obstructed from reaching the unit.

Clearance of at least 6 ft on all sides is required.

ROUTINE MAINTENANCE AND CARE

FOR THE EQUIPMENT OWNER

Before proceeding with those things you might want to maintain

yourself, please carefully consider the following:

FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,

death, and/or property damage.
1.Turn off gas supply and electrical power to your unit before

servicing or performing maintenance.

2. Do not turn off electrical power to this unit without first

turning off gas supply and applying lockout tags.

3. When removing access doors or performing maintenance

functions inside your unit, be aware of sharp sheet metal

parts and screws. Although special care has been taken to

reduce sharp edges to a minimum, be extremely careful

when handling parts or reaching into the unit.

!

WARNING

Air Filter(s)

Air filters should be checked at least every 3 or 4 weeks and
changed or cleaned whenever they become dirty. Table 1 indicates

the correct filter size for your unit. Open the filter access panel to

replace or inspect the filters. All units have filter tracks into which
the filters slide. Remove the filters by pulling the filter slide

outward from the track. See Fig. 6 for filter access panel location.
Note the direction of flow arrows on the filter frame.
If you have difficulty in locating your air filter in the return--air
duct system, or if you have questions concerning proper filter

maintenance, contact your dealer for instructions. When replacing

your unit filters, always use the correct size and quantity as shown
in Table 1. Filter tracks are field convertible for 2 or 4--in. thick

filters. Verify airflow and duct static values, and related motor
sizing and belt drive adjustment, if filter type or efficiency rating is

changed from the original installation.
Units with outdoor air capability have cleanable screens for the
outdoor air. These screens should be checked annually and cleaned

as necessary.

FIRE AND EQUIPMENT DAMAGE HAZARD
Failure to follow this warning could result in personal injury,

death, and/or property damage.
Never operate unit without filters in place. Damage to blower

motor and/or compressors could result. An accumulation of

dust and lint on internal parts of your unit can cause loss of

efficiency and in some cases, fire.

!