Step 10 —

Set room thermostat selector slightly above room

temperature and set system switch to HEAT position to start the
unit. The induced--draft combustion air fan will start. Main burners
light within 30 seconds. Indoor blower will start within 60 to 90
seconds of main gas ignition.

Step 11 —

Set the temperature selector on room thermostat to

desired setting.

INDUCED
DRAFT
MOTOR

COMBUSTION
FAN HOUSING

MAIN GAS
VALVE

MAIN BURNER SECTION

HEAT EXCHANGER
SECTION

C06258

Fig. 1 -- Typical Gas Heating Section

FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,

death, and/or property damage.
If the main burners fail to light, or the blower fails to come on,

shut down gas heating section and call your dealer for service.

!

WARNING

TO LIGHT UNIT

(UNITS WITH COMFORTLINK

t

CONTROL)

FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,

death, and/or property damage.
1. Do not turn off the electrical power to unit without first

turning off the gas supply and applying lockout tags.

2. Before attempting to start the gas heating section, familiarize

yourself with all the procedures that must be followed.

3. Never attempt to manually light the burners on the unit with

a match, lighter, or any other flame. If the electric sparking

device fails to light the burners, refer to the shutdown

procedures, then call your dealer as soon as possible.

!

DANGER

See Fig. 1. for location of gas valve. Refer to Fig. 3 while
proceeding with the following steps:

Step 1 —

Turn off the unit by using the Scrolling Marquee to

put the unit into Service Test mode. The Scrolling Marquee is
located on the front of the unit control box behind the control box
and compressor access door. Thermostat inputs and remote
network commands are ignored when Service Test mode is ON.
NOTE: A password may be required to change Service Test
values, depending on previous settings configured in the unit.
Default password is “1111.”

a. Press the ESCAPE key until a blank screen is shown.

b. Use the arrow keys to scroll the red LED on the display

to the “Service Test” position and press ENTER.

c. The control will display the Field Service Test Mode

(TEST) setting. Press ENTER once to select the TEST
setting for configuration. Press ENTER again for “OFF”

to begin flashing.

d. Use the arrow keys to change the configuration from

“OFF” to “ON,” then press ENTER to save the setting.

Step 2 —

Close the shutoff valve on the gas supply piping.

Step 3 —

Turn off the electrical supply to the unit and install

lockout tag.

Step 4 —

Open the heat section access panel.

Step 5 —

Move ON/OFF switch on the internal gas valve to the

OFF position and wait 5 minutes.

Step 6 —

Move ON/OFF switch on internal gas valve to ON

position.

Step 7 —

Close the heat section access panel.

Step 8 —

Remove lockout tag and turn on the electrical supply

to unit.
NOTE: Normal operation will automatically begin. Service Test
mode will automatically end (exit) after a recycle of power.

Step 9 —

Open the shutoff valve on the external gas supply

piping.

Step 10 —

To test the operation of the gas section, the HEAT

submenu of Service Test may be used. See the Controls, Start--Up,
Operation, Service, and Troubleshooting Instructions for more
details on use of Service Test.

Step 11 —

For normal operation, make sure that the set points

are at the normal heat set points.

FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,

death, and/or property damage.
If the main burners fail to light, or the blower fails to come on,

shut down gas heating section and call your dealer for service.

!

WARNING

48PD

,48PG