Table i- ratings and capacities – Bryant UNIT 379H User Manual

Page 2

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

- s s l -

-76f-

UNIT
SIZE

CONNECTION
SIZE (COIL)

A

B

c

D

7/8 OD
(Suction)*

2 ea 6-3/16

14-13/16

180R-379H

5/8 OD (Liquid)*

2 ea

10-3/16

18-13/16

1-3/8 OD
(Suction)

2 ea 7-3/16

12-5/8

240R-379H

5/8 OD (Liquid)

2 ea

10-3/16

18-1/2

*Refer to condensing unit for compressor suction and liquid line sizes

Approximate

Shipping Weights

450-379H—1425 lbs

180R-379H—1460 lbs
240R-379H—1565 lbs

^4

Figure 2-Dimensional Drawing

A69420

TABLE I- Ratings and Capacities

• Model 450-, 180R-, & 240R-379H

Heating Input, 1st Stage

Btuh

225,000

Heating Output, 1st Stage

Btuh

168,000

Heating Input, 1st & 2nd Stages

Btuh

450,000

Heating Output, 1st & 2nd Stages

Btuh

337,000

Approved Temp Rise

°F

20-75

CFM 0.5 inch wc S.P.

6,000

Blower Motor

HP

3

Power Supply

208-60-3

230-60-3

Full Load Current

Amps

8.4

8.4

Locked Rotor Current

Amps

58.2

53.0

Speed

RPM

3450

Frame Size

56

Branch Circuit Wire Size Min*

AWG No.

14

14

Branch Circuit Fuse Size Max

Amps

25

25

Filters

Size

(450-379H) (6) 16x25x1

(180R & 240R) (3) 16x25x1

(3) 20x25x1

*If alumimun conductors are to be used, the connections must be made in accordance with the National Electric Code. The

wire size selected must have a current capacity not less than that of the copper wire specified and must not create a voltage
drop between the service panel and the unit in excess of 2% of the unit rated voltage.

-

2

-