Table 1G — Electrical Data (COBRA™ Energy Recovery 48HJ008-014 Units with 62AQ300)
LEGEND
*Used to determine minimum disconnect per NEC.
†Single point box CRSINGLE017A00 is part of base unit.
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. UL, Canada units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percent of voltage imbalance.
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
UNIT
NOMINAL
V-PH-Hz
IFM
TYPE
CONV
OUTLET
62AQ
FLA
POWER SUPPLY
DISCONNECT SIZE*
MCA
FUSE OR
HACR BKR
FLA
LRA
48HJ008
208/230-3-60
STD
NO
29.8
68.0
80
75
420
STD
YES
29.8
74.0
80
80
425
HIGH STATIC
NO
29.8
71.1
80
78
445
HIGH STATIC
YES
29.8
77.1
80
84
449
460-3-60
STD
NO
15.8
35.0
40
38
211
STD
YES
15.8
37.7
40
41
213
HIGH STATIC
NO
15.8
36.4
40
40
224
HIGH STATIC
YES
15.8
39.1
45
43
226
48HJ009
208/230-3-60
STD
NO
29.8
70.0
80
77
454
STD
YES
29.8
76.0
80
82
459
HIGH STATIC
NO
29.8
73.1
80
80
479
HIGH STATIC
YES
29.8
79.1
80
86
483
460-3-60
STD
NO
15.8
37.3
40
41
233
STD
YES
15.8
40.0
45
43
235
HIGH STATIC
NO
15.8
38.7
45
42
246
HIGH STATIC
YES
15.8
41.4
45
45
248
48HJ012
208/230-3-60
STD
NO
29.8
82.8
90
90
519
STD
YES
29.8
88.8
100
96
523
HIGH STATIC
NO
29.8
87.2
100
95
542
HIGH STATIC
YES
29.8
93.2
100
101
547
460-3-60
STD
NO
15.8
40.7
45
44
261
STD
YES
15.8
43.4
45
47
263
HIGH STATIC
NO
15.8
43.3
50
47
272
HIGH STATIC
YES
15.8
46.0
50
50
274
48HJ014
208/230-3-60
STD
NO
29.8
90.4
100
98
604
STD
YES
29.8
96.4
100
104
609
460-3-60
STD
NO
15.8
44.9
50
49
297
STD
YES
15.8
47.6
50
51
299
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
UL
— Underwriters’ Laboratories
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
7
457