beautypg.com

Carrier COBRA 48/50HJ004-014 User Manual

Page 24

background image

24

Table 1G — Electrical Data (COBRA™ Energy Recovery 48HJ008-014 Units with 62AQ300)

LEGEND

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:
1. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. UL, Canada units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percent of voltage imbalance.

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

UNIT

NOMINAL

V-PH-Hz

IFM

TYPE

CONV

OUTLET

62AQ

FLA

POWER SUPPLY

DISCONNECT SIZE*

MCA

FUSE OR

HACR BKR

FLA

LRA

48HJ008

208/230-3-60

STD

NO

29.8

68.0

80

75

420

STD

YES

29.8

74.0

80

80

425

HIGH STATIC

NO

29.8

71.1

80

78

445

HIGH STATIC

YES

29.8

77.1

80

84

449

460-3-60

STD

NO

15.8

35.0

40

38

211

STD

YES

15.8

37.7

40

41

213

HIGH STATIC

NO

15.8

36.4

40

40

224

HIGH STATIC

YES

15.8

39.1

45

43

226

48HJ009

208/230-3-60

STD

NO

29.8

70.0

80

77

454

STD

YES

29.8

76.0

80

82

459

HIGH STATIC

NO

29.8

73.1

80

80

479

HIGH STATIC

YES

29.8

79.1

80

86

483

460-3-60

STD

NO

15.8

37.3

40

41

233

STD

YES

15.8

40.0

45

43

235

HIGH STATIC

NO

15.8

38.7

45

42

246

HIGH STATIC

YES

15.8

41.4

45

45

248

48HJ012

208/230-3-60

STD

NO

29.8

82.8

90

90

519

STD

YES

29.8

88.8

100

96

523

HIGH STATIC

NO

29.8

87.2

100

95

542

HIGH STATIC

YES

29.8

93.2

100

101

547

460-3-60

STD

NO

15.8

40.7

45

44

261

STD

YES

15.8

43.4

45

47

263

HIGH STATIC

NO

15.8

43.3

50

47

272

HIGH STATIC

YES

15.8

46.0

50

50

274

48HJ014

208/230-3-60

STD

NO

29.8

90.4

100

98

604

STD

YES

29.8

96.4

100

104

609

460-3-60

STD

NO

15.8

44.9

50

49

297

STD

YES

15.8

47.6

50

51

299

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

UL

Underwriters’ Laboratories

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.

7
457