beautypg.com

Carrier COBRA 48/50HJ004-014 User Manual

Page 21

background image

21

Table 1E — Electrical Data (COBRA™ Energy Recovery 48HJ008-014 Units with 62AQ200)

LEGEND

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:
1. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. UL, Canada units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percent of voltage imbalance.

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

UNIT

NOMINAL

V-PH-HZ

IFM

TYPE

CONV

OUTLET

62AQ

FLA

POWER SUPPLY

DISCONNECT SIZE*

MCA

FUSE OR

HACR BKR

FLA

LRA

48HJ008

208/230-3-60

STD

NO

21.9

60.1

70

66

366

STD

YES

21.9

66.1

70

71

371

HIGH STATIC

NO

21.9

63.2

70

69

391

HIGH STATIC

YES

21.9

69.2

80

75

395

460-3-60

STD

NO

10.2

29.4

35

32

184

STD

YES

10.2

32.1

35

34

186

HIGH STATIC

NO

10.2

30.8

35

34

197

HIGH STATIC

YES

10.2

33.5

35

36

199

48HJ009

208/230-3-60

STD

NO

21.9

62.1

70

68

400

STD

YES

21.9

68.1

70

73

405

HIGH STATIC

NO

21.9

65.2

70

71

425

HIGH STATIC

YES

21.9

65.2

70

71

425

460-3-60

STD

NO

10.2

31.7

35

34

206

STD

YES

10.2

34.4

40

37

208

HIGH STATIC

NO

10.2

33.1

35

36

219

HIGH STATIC

YES

10.2

35.8

40

38

221

48HJ012

208/230-3-60

STD

NO

21.9

74.9

80

81

465

STD

YES

21.9

80.9

90

87

469

HIGH STATIC

NO

21.9

79.3

90

86

488

HIGH STATIC

YES

21.9

85.3

90

92

493

460-3-60

STD

NO

10.2

35.1

40

38

234

STD

YES

10.2

37.8

40

40

236

HIGH STATIC

NO

10.2

37.7

40

41

245

HIGH STATIC

YES

10.2

40.4

45

43

247

48HJ014

208/230-3-60

STD

NO

21.9

82.5

90

89

550

STD

YES

21.9

88.5

100

95

555

460-3-60

STD

NO

10.2

39.3

45

43

270

STD

YES

10.2

42.0

45

45

272

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

UL

Underwriters’ Laboratories

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.

7
457