Table 1B — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ060) (cont)

LEGEND

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective device
for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or cir-
cuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.
Use the following formula to determine the percent of voltage
imbalance.

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.

UNIT

NOMINAL

V-PH-Hz

IFM

TYPE

CONV

OUTLET

62AQ

FLA

HEATER

CRHEATER

---A00

HEAT

POWER SUPPLY

SINGLE

POINT BOX

CRSINGLE

---A00

DISCONNECT SIZE*

FLA

MCA

FUSE OR

HACR BKR

MOCP

FLA

LRA

50HJ005

(cont)

460-3-60

STD

YES

9.2

NONE

17.9

20

21

75

006

7.2

18.8

25

21

75

008

13.8

27.1

30

21

75

009

16.8

30.8

35

025

32

75

008+008

27.7

44.4

45

025

44

75

HIGH STATIC

NO

9.2

NONE

15.6

20

16

84

006

7.2

17.1

20

16

85

008

13.8

25.4

30

19

85

009

16.8

29.1

30

28

85

008+008

27.7

42.7

45

025

40

85

HIGH STATIC

YES

9.2

NONE

18.3

20

22

89

006

7.2

19.2

25

22

90

008

13.8

27.5

30

22

90

009

16.8

31.2

35

025

32

90

008+008

27.7

44.8

45

025

45

90

50HJ006

208/230-1-60

STD

NO

9.2

NONE

—/—

55.5/ 55.5

70/70

56/ 56

250/250

002

23.5/27.1

55.5/ 55.5

70/ 70

004

56/ 56

250/250

003

31.4/36.3

59.5/ 65.5

70/ 70

004

57/ 62

250/250

002+002

46.9/54.2

78.9/ 87.9

80/ 90

005

75/ 83

250/250

003+003

62.8/72.5

98.7/110.8

100/125

005

93/104

250/250

004+004

75.8/87.5

115.0/129.6

125/150

005

108/121

250/250

STD

YES

9.2

NONE

—/—

61.5/ 61.5

70/70

61/ 61

255/255

002

23.5/27.1

61.5/ 61.5

70/ 70

004

61/ 61

255/255

003

31.4/36.3

64.3/ 69.7

70/ 70

005

62/ 67

255/255

002+002

46.9/54.2

83.7/ 92.1

90/100

005

80/ 88

255/255

003+003

62.8/72.5

103.5/115.0

110/125

005

98/109

255/255

004+004

75.8/87.5

119.8/133.8

125/150

005

113/126

255/255

208/230-3-60

STD

NO

9.2

NONE

—/—

38.1/ 38.1

45/45

39/ 39

202/202

002

13.6/15.6

38.1/ 38.1

45/45

39/ 39

202/202

004

21.9/25.3

44.1/ 48.3

50/50

42/ 46

202/202

005

33.4/38.5

58.4/ 64.9

60/ 70

002

56/ 62

202/202

004+004

43.8/50.5

71.5/ 79.9

80/ 80

003

68/ 75

202/202

004+005

55.2/63.8

85.8/ 96.4

90/100

003

81/ 91

202/202

STD

YES

9.2

NONE

—/—

44.1/ 44.1

50/50

44/ 44

207/207

002

13.6/15.6

44.1/ 44.1

50/50

44/ 44

207/207

004

21.9/25.3

48.9/ 52.5

60/60

48/ 51

207/207

005

33.4/38.5

63.2/ 69.1

70/ 70

003

61/ 66

207/207

004+004

43.8/50.5

76.3/ 84.1

80/ 90

003

73/ 80

207/207

004+005

55.2/63.8

90.6/100.6

100/110

003

86/ 95

207/207

HIGH STATIC

NO

9.2

NONE

—/—

39.8/ 39.8

45/45

41/ 41

221/221

002

13.6/15.6

39.8/ 39.8

45/45

41/ 41

221/221

004

21.9/25.3

45.9/ 50.1

50/60

44/ 48

221/221

005

33.4/38.5

60.3/ 66.7

70/ 70

003

58/ 63

221/221

004+004

43.8/50.5

73.3/ 81.7

80/ 90

003

70/ 77

221/221

004+005

55.2/63.8

87.6/ 98.3

90/100

003

83/ 93

221/221

HIGH STATIC

YES

9.2

NONE

—/—

45.8/ 45.8

50/50

46/ 46

226/226

002

13.6/15.6

45.8/ 45.8

50/50

46/ 46

226/226

004

21.9/25.3

50.7/ 54.3

60/60

50/ 53

226/226

005

33.4/38.5

65.1/ 70.9

70/ 80

003

63/ 68

226/226

004+004

43.8/50.5

78.1/ 85.9

80/ 90

003

75/ 82

226/226

004+005

55.2/63.8

92.4/102.5

100/110

003

88/ 97

226/226

460-3-60

STD

NO

9.2

NONE

19.3

25

20

101

006

7.2

19.3

25

20

101

008

13.8

25.4

30

20

101

009

16.8

29.1

30

28

101

008+008

27.7

42.7

45

025

40

101

008+009

30.7

46.4

50

025

44

101

STD

YES

9.2

NONE

22.0

25

25

106

006

7.2

22.0

25

25

106

008

13.8

27.5

30

25

106

009

16.8

31.2

35

025

32

106

008+008

27.7

44.8

45

025

45

106

008+009

30.7

48.5

50

025

48

106

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

UL

Underwriters’ Laboratories

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.

7
457