ELECTRICAL DATA (Cont)
ELECTRICAL DATA (60-Hz)
V/PH
VOLTAGE
RANGE
UNIT
COMPR*
IFM OFM
WSA ICF
FU
FLA
LRA
FLA (ea)
208/3
220-180
79.6
152
100
27.60
1 10
10.6
3.2
230/3
254-198
70 0
137
90
23.80
100
9.2
3 2
460/3
506-414
33 9
69
45
11 85
50
4.6
1 2
IFM
— Indoor Fan Motor
LRA
— Locked Rotor Amps
OFM
— Outdoor Fan Motor
WSA
— Wire Sizing Amps per NEC equals 1 25
X
FLA of the largest
motor
plus
the
sum
of
the
FLA
of
all
other
motors
in
the unit.
*Unit has two compressor motors; values are for each.
FLA
— Full Load Amps
FU
— Fuse (max allowable amps)
ICF
—Max Instantaneous Current Flow during start-up is the sum of
compressor LRA plus the FLA of all other motors in the unit