Dimensions, Selection procedure (with example), Dimensions physical data – Carrier 48DD User Manual
Page 2
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

DIMENSIONS
PHYSICAL DATA
U N I T 4 8 D D
0 1 2
O P E R A T I N G W E I G H T ( l b )
1 6 9 0
R E F R I G E R A N T
2 2
O p e r a t i n g C h a r g e ( I b )
9 e a c h S y s t e m
C O M P R E S S O R
( 2 ) R e c i p r o c a t i n g H e r m e t i c
C y l i n d e r s . . . R p m ( 6 0 - H z )
4 e a c h 3 5 0 0
O U T D O O R A I R F A N S
P r o p e l l e r ; D i r e c t D r i v e
N o . . . . D i a m ( i n . )
2 2 2
N o m C f m e a c h . . . t o t a l
3 2 0 0 . 6 4 0 0
1 / 1 1 4 0 ( 3 - p h a s e )
M o t o r H p . . . R p m
1 0 7 5 ( 1 - i ^ h a s e )
C O N D E N S E R C O I L
P l a t e F i n
R o w s . . . F i n s / i n .
4 1 3
T o t a l F a c e A r e a ( s q f t )
1 4 0
I N D O O R A I R F A N S
C e n t r i f u g a l ; B e l t D r i v e
N o . . . . S i z e ( i n . )
2 1 0 x 1 0
N o m C f m
4 0 0 0
R p m R a n g e ( S t a n d a r d D r i v e )
1 2 3 0 t o 1 5 4 0
M a x A l l o w a b l e R p m
1 7 0 0
B e l t T y p e . . . L e n g t h ( i n . )
A . 4 4
M o t o r
N o . . . . H p . . . R p m
1 3 1 7 4 5
M a x B r a k e H p
3 4 5
F r a m e
1 8 2 T
S h a f t D i a m ( i n . )
i V s
P u l l e y P i t c h D i a m ( i n . )
5 6
E V A P O R A T O R C O I L
P l a t e F i n
T o t a l F a c e A r e a ( s q f t )
1 0 0 2
R o w s . . . F i n s / i n .
3 1 4
H E A T E X C H A N G E R S
A l u m i n i z e c d S t e e l
A . G . A . C e r t i f i e d R i s e
4 5 t o 7 5 F
N o . . . . E l e m e n t s ( e a c h )
2 . 5
SELECTION PROCEDURE (With Example)
I Determine cooling and heating requirements at design
conditions.
GIVEN;
Required Cooling Capacity (TO
Sensible Heat Capacity (SHC)
Required Heating Capacity
Condenser Entering Air Temp
Indoor Air Temp
Evaporator Air Quantity
Electrical Characteristics
External Static Pressure
128.000
Btuh
90,000 Btuh
198.000
Btuh
. 95 F
80 F Edb, 67 Ewb
4000 Cfm
230-3-60
8 in. wg
II Select unit based on required cooling capacity.
Enter
Cooling
Capacities
table
at
condenser
entering
air
tempera
ture
of
95
F.
The
48DD012
at
4000
cfm
and
67
F
Ewb
will
provide
a
total
capacity
of
132,000
Btuh
and
a
sensible
heat
of
96,000 Btuh Calculate SHC correction if required
III Compare the heating capacity of the unit selected with the
design conditions.
Unit
48DD012
provides
an
input
of
275,000
Btuh
with
a
bonnet
capacity of 206,000 Btuh
IV Determine fan speed and brake hp requirements at design
conditions.
Enter
Fan
Performance
table.
At
4000
cfm
and
8
in
wg,
the
fan
speed is 1 405 rpm and brake hp is 2.34 The table indicates that
standard drive is adequate.
V Select unit that corresponds to available power source.
Refer
to
Electrical
Data
table
and
choose
unit
as
required
A
48DD012 230-3-60 is available.