beautypg.com

Operating the unit, A. selecting the correct voltage – Winco MD25K/C User Manual

Page 8

background image

Page 6

41821

60706-120

normally. If frequency has not returned at the end of

this time period, the engine oil pressure status is

observed to determine whether the engine is actually

running or stopped. If the engine has stopped (i.e.- air in

fuel, (etc), the unit is shut down with an “overspeed”

indication and alarm.

b. “Overspeed” indicator light can mean a loss of control

signal during the previous run period (i.e.- bat. charging

alternator belt broken).

TROUBLE SHOOTING HINT: This is of particular

note since the tendency is to pursue only overspeed

faults. The overspeed signal source (battery charging

alternator) is a key component in this system and must

be checked out thoroughly whenever an “OS” shutdown

occurs.

Please note: The controller does not provide protection

against loss of signal during start-up. A shutdown with

alarm due to any of the above conditions will prevent

any subsequent operation of the generator set. The

control switch on the control panel must be momentarily

placed in the “off” position to reset.

D. VOLT/HERTZ VOLTAGE

REGULATOR

The purpose of the voltage regulator is to maintain the

voltage output of the Generator Set within a specified

percentage of its rated output from no load to full load.

The voltage regulator controls the voltage output of the

main generator by regulating the amount of current

delivered to the exciter field.

1. Location -Access to the voltage regulator assembly is

gained by removing the control panel access door located

through the left rear housing door.

2. Description - The Basler model VR63-4C voltage

regulator is a completely encapsulated unit. The regula-

tor controls the DC exciter field voltage on brushless

generators to regulate the output voltage. Regulation is

provided by sensing the generator output voltage,

converting it to a DC signal and comparing the signal to

a reference voltage signal. An error signal is developed

and used to control the DC field power in order to

maintain a constant generator output.

3. Operation of voltage regulator - The voltage regulator

has been installed in the Mobile Diesel Generator set

and tested at the factory prior to shipment. No addi-

tional set-up is required when changing from one voltage

to another. The only adjustment required is to fine tune

the exact voltage you want using the voltage adjustment

rheostat located on the front panel. The adjustment

range is 10% of the nominal voltage.

Some minor changes must be made for 50 cycle opera-

tion. Refer to 50 Hz operation later in this section for

set-up procedures.

a. During periods of operation at reduced speed use the

field circuit breaker to remove the power from the

regulator.

b. If the exciter field voltage exceeds 95 VDC, the regula-

tor senses overexcitation and automatically removes the

field current after a time delay. This time delay is

inversely proportional to the magnitude of the detected

overvoltage condition. At approximately 140 VDC, the

field voltage is removed instantaneously.

Upon detection of overexcitation and the resulting field

voltage shutdown, the regulator will not reset or return

to an operational condition until the generator output

voltage drops to less than 6 VAC for ten seconds (mini-

mum). TO ACCOMPLISH THIS ON A MOBILE DIE-

SEL GENERATOR SET THE FIELD CIRCUIT

BREAKER MUST BE TURNED OFF FOR TEN SEC-

ONDS.

For additional information on the Basler Voltage regula-

tor model APR125-5X see Basler Electric publication

number: 9 1688 00 992.

OPERATING THE UNIT

A. SELECTING THE CORRECT

VOLTAGE

A variety of voltages are available from the three posi-

tion selector switch. The three basic connection patterns

are, Delta (120/240), Low or Parallel WYE (120/208),

and High WYE (277/480). Single phase 120/240 is

available with the switch in the 120/240 (Delta) position.

Before connecting this unit to a distribution panel or any

other loads, be sure you have the selector switch set for

the right voltage and locked. If you have any doubts as

to the voltage in your area compare your incoming

power or load name plates to the voltage table below.

1. 120/240 Three Phase* (Delta/Series configuration) -

This configuration will produce the following line-to-line

and line-to-neutral voltage. In this selector switch

position, all of the receptacles on the front panel are

powered.

L1 - L2 - L3 240 Volts three phase

L1 - L2 240 volts single phase

L2 - L3 240 volts single phase

L1 - L3 240 volts single phase

L1 - N 120 Volts

L2 - N 120 Volts

L3 - N 208 volts