Winco MD25K/C User Manual

Page 6

background image

Page 4

41821

60706-120

coolant temperature gauge indicates engine coolant

temperature. The gauge serves a dual function. In

addition to displaying the water temperature it also

provides the shutdown signal to the engine control

module if the water temperature gets too high. The

shutdown signal is preset to operate at 225 f (407 k)

c. Battery Voltage Meter - This DC voltmeter monitors

the VOLTAGE of the battery under static (at rest)

conditions, and under cranking and charging conditions.

The voltmeter indicates not only the condition of the

charging system, but also indicates the battery reserve

under cranking load in cold weather.

d. Running Time Meter - This DC meter records the

total hours the engine has run.

6. A.C. Generator Controls

a. Voltage adjust rheostat - Controls the output voltage

of the generator by varying voltage regulators reference

voltage.

b. Field circuit breaker (FCB) - Protects voltage regula-

tor and exciter field in the event of a load short circuit or

equipment malfunction.

c. Voltage selector power switch - This heavy duty three

position switch allows the operator to quickly and safely

reconnect the 12 wire generator to any one of three

output voltages. Once the output voltage is selected, the

switch may be locked to prevent it from accidentally

being changed during operation. Three output voltage

combinations are available with this selector switch:

1. 120/240 Three Phase* (series Delta configuration)

2. 120/208 Three Phase (Low or Parallel “WYE” configu-

ration)

3. 277/480 Three Phase (High or series “WYE” configu-

ration)

*This selector position is also used for single phase 120/

240 output by using only the L1 and L2 leads. The three

phase L3 output lead is the “wild” leg in the delta

configuration.

5. AC Generator Instruments

a. VM/AM Selector Switch - This selector switch allows

you to check the amperage being drawn from each

generator leg and your line to line voltage.

a. AC Voltmeter (VM) - Monitors generator output line to

line voltage, for all voltage operations.

b. AC Ammeter (AM) - Monitors the amperage that is

being drawn from each leg of the generator.

c. AC Frequency Meter - Monitors the generator fre-

quency.

7. Warning Light Cluster - This light cluster contains

the indicator lamps for the four engine shutdowns

controlled by the engine control module. The lamps will

stay lit after a shutdown until the selector switch has

been moved to the off position. All the shutdowns are

reset when the selector switch is turned off or the DC

circuit breaker is turned off.

a. Low Oil Pressure Lamp (LOP) - Indicates that the

unit did not maintain a minimum oil pressure of 15 psi.

b. High Water Temperature Lamp (HWT) - Indicates

the coolant temperature in the engine exceeded upper

coolant temperature limits.

c. Overspeed Lamp (OS) - Indicates the engine speed

exceeded the allowable speed limit while operating. An

OS light may also indicate that the ECM has lost its

frequency sensing signal (from the engine alternator)

during the last run period.

d. Overcrank Lamp (OC) - Indicates the engine tried to

start and went through five (5) twelve (12) second crank

cycles without starting. Before attempting to restart the

unit, first investigate why it didn’t start.

e. Lamp Test Switch - The lights can be tested by

pressing the lamp test switch. When depressed all four

lights will come on. As soon as the switch is released the

light will go out.

8. Panel Light - A panel light is provided for your

convenience. It is activated by the panel light switch.

9. Receptacles and Circuit Breakers - All of the

receptacles on the panel are protected by circuit break-

ers.

a. 120 Volt 20 Amp Ground Fault Interputer Duplex.

This duplex receptacle is protected by a 20 Amp circuit

breaker mounted just above the duplex. With the “T”

slot design both 15 and 20 amp 120 volt cords can be

plugged in.

b. 120 Volt 20 Amp 3 wire twist lock, Nema Spec L5-20.

This twistlock receptacle is also protected by a 20 Amp

circuit breaker. This receptacle is wired in series with

the GFCI receptacle which provides it with GFCI

protection.

c. 240 Volt 20 Amp 3 wire twist lock, Nema Spec L6-20.

This twistlock receptacle is protected by a two pole 240

volt circuit breaker.

d. 120/240 Volt 50 Amp 4 wire twistlock. This receptacle

is rated for dual voltage, 120 or 240 volt use. It is a four

wire receptacle, with a center grounding pin. Four wire