41821

60706-120

SPECIFICATIONS

GENERATOR SPECIFICATIONS

MD25

KILOWATT

20 KW

KILOVOLT-AMPS

(.8 PF)25 KVA

AMPERAGE 277/480 VOLT 3 PHASE 30 AMPS*

120/240 VOLT 3 PHASE 60 AMPS*

120/208 VOLT 3 PHASE 69 AMPS*

120/240 VOLT 1 PHASE 80 AMPS

*Based on .8 power factor at 130 degrees C.

Derate 3% per 1000 feet (305 meters) between 300 feet

(90 meters) and 7,500 feet (2,286 meters) above sea level.

Contact the factory for rating data for operation in

altitudes above 7,500 feet (2,286 meters).

GENERATOR RESISTANCES

MD25

Main Stator

.20 ohms

Main Rotor

3.5 ohms

Excitor Stator

25 ohms

Excitor Rotor

.350 ohms

Excitor Voltage (F1-F2)

No Load

15 VDC

Full Load

34 VDC

Excitor Amperage (F1-F2)

No Load

.58 Amps

Full Load

1.3 Amps

ENGINE SPECIFICATIONS

See Kubota Operation and Maintenance Manual for

complete engine specifications.

TRAILER/HOUSING

MD25

Capacity

3500 lbs

Fuel Capacity

45 gals

Axles

Single

Hitch Height

Fixed

Tires

P215/75B15 4 Ply Tread

Tire Pressure

35 psi

Sound Attenuated

ULTRA QUIET

Housing

Housing Standard

PREPARATION

NOTE: This booklet covers the entire unit, EXCEPT

THE ENGINE. See the engine manufacturer’s operator

manual for specific maintenance and care information

regarding the engine. Read ALL instructions in the

manuals provided before attempting to operate the

generator set.

UNPACKING

When unpacking the unit, be sure to inspect it carefully

for freight loss or damage. Check the nameplate to be

sure it is what you ordered (proper KW, voltage, fuel,

etc.). If you have questions, contact your local authorized

dealer. If you see evidence of loss or damage at the time

of delivery, have the driver sign and describe the loss or

damage in the “memo of loss or damage” section on the

freight bill. Then contact the carrier to get instructions

on filing a claim.

When loss or damage is discovered after the equipment

is delivered, but not seen at the time of delivery, it is

referred to as “concealed damage.” Separate any dam-

aged material and contact the carrier for proper proce-

dures to file a “concealed damage” claim.

OIL REQUIREMENTS

The use of a multi-grade lubricating oil has been found

to improve oil consumption control and improve engine

cranking in cold temperatures while maintaining

lubrication at high operating temperatures. A multi-

graded oil 10W-30 or 10W-40 is recommended, meeting

API Classification CC/CD/CE. See your engine operators

manual for recommended oil grades when operating in

extreme cold conditions (ambients under -10 deg. C.) and

Arctic conditions.

OIL QUANTITY

US Qts.

Liters

MD25

10.1

9.5

FUEL REQUIREMENTS

ASTM No.2 diesel fuel is recommended for these en-

gines. The use of No. 2 diesel fuel will result in optimum

engine performance. The use of lighter fuel will reduce

fuel economy. See your engine operators manual for

complete fuel information.

Filling the Fuel Tank

Standard Trailer - The standard trailer is equipped with

single a 45 gallon fuel tank. Use caution when filling the

tank not to overflow the tank into the trailer.

WARNING PERSONAL DANGER

Never refuel a running engine,. Always stop the engine

and allow to cool before refueling.

Never allow the fuel tank to run completely empty, as

air may enter the fuel system making it necessary to

bleed the engine when restarting.